Cooling / Heating Correction Factors
For Single Zone Wall Mounted Extended Piping systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor
unit. Also, determine the elevation difference of the indoor unit above or below the outdoor unit. Find the corresponding cooling or heating
capacity correction factors as shown in the table below. Multiply the correction factors by the cooling or heating capacity obtained from the
capacity tables using design conditions. The resultant is the NET cooling or heating capacity.
EQUIPMENT SELECTION PROCEDURE
Table 17:
Single Zone Wall Mounted Extended Piping Cooling/Heating % Coefficient Factors.
Model
Main Piping Length
Indoor Unit
Outdoor Unit
Feet
24.6
32.8
49.2
65.6
82
98.4
114.8
131.2
147.6
164
LSN243HLV
LSU243HLV
Cooling
100
99.6
98.7
97.8
96.9
96.0
95.1
94.3
93.4
92.5
Heating
100
99.8
99.3
98.9
98.4
98.0
97.5
97.1
96.6
96.2
LSN303HLV
LSU303HLV
Cooling
100
99.6
98.7
97.8
96.9
96.0
95.1
94.3
93.4
92.5
Heating
100
99.8
99.3
98.9
98.4
98.0
97.5
97.1
96.6
96.2
LSN363HLV
LSU363HLV
Cooling
100
99.6
98.7
97.8
96.9
96.0
95.1
94.3
93.4
92.5
Heating
100
99.8
99.3
98.9
98.4
98.0
97.5
97.1
96.6
96.2