- 64 -
Check the connector of intake and pipe sensor(thermistors)
• Check the related circuit of R02H(12.1K), R01H(1.0K), R04H(6.2K),
R03H(1.0K), Micom(No. 3, 4).
• Check the indoor room temperature is disconnected or not (about
10K
Ω
/at 25°C).
• Check the indoor pipe temperature is disconnected or not (about
5K
Ω
/at 25°C).
Check the DC voltage on the PWB ASS’Y
• The details of check are as followings
Check point
Between Micom
(NO.62) and GND
Between IC01M
(NO.14) and GND
Comp ON
DC 5V
Below DC 1V
Comp OFF
DC 0V
About DC
12V
Check point
Between Micom
(NO.54) and GND
Between IC02M
(NO.16) and GND
4 way ON
DC 5V
Below DC 1V
4 way OFF
DC 0V
About DC 12V
Check point
Between Micom
(NO.53) and GND
Between IC02M
(NO.15) and GND
Fan ON
DC 5V
Below DC 1V
Fan OFF
DC 0V
About DC 12V
• Comp Relay.
• 4 way Relay
• Outdoor fan Relay
Turn off Main Power
• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of
Compressor/Outdoor Fan Motor, 4 way.
• Check the "open" or "short" of connecting wires between indoor and
outdoor.