4. Cooling mode operation
• Operating frequency of compressor depend on the difference of the temperature.
(= intake air Temp.- Compressor off Temp.
• Compressor off temp.= setting temp. -0.5°C
on temp. = setting temp. +0.5°C
• If compressor operates at some operating frequency, the operating frequency of compressor cannot be
changed within 30 seconds.
• Condition of compressor turned off
- When intake air temperature stay at the temperature between setting temp. -0.5°C and setting temp.
-1.0°C for 3 minutes continuously.
- When intake air temperature reaches below the temperature of setting temp. -1.0°C.
• Compressor 2 minutes delay
- The compressor can restart minimum 2 minutes later after compressor off.
Temp. differences
over 2.5°C
2.0~2.49°C
1.5~1.99°C
1.0~1.49°C
0.5~0.99°C
0.0~0.49°C
Comp. Operating frequency
Step 12
Step 10
Step 8
Step 4
Step 2
Step 1
[The operating freq. step of comp.]
[The targeting operating freq. of comp. each model]
Model
7K Btu Series
9K Btu Series
12K Btu Series
18K Btu Series
Comp. Operating frequency
40
47
54
64
74
85
45
53
72
86
95
110
35
47
51
58
62
67
35
47
57
66
71
96
Step 1
Step 2
Step 4
Step 8(Fc)
Step 10
Step 12