2. Protection of the evaporator pipe from frosting
• If the indoor pipe temperaure is below 0°C in 7 min. after the compressor operates without pause while in
cooling cycle operation mode,
➔
compressor, outdoor fan are turned off.
• When indoor pipe temp. is 7°C or higher after 2 min pause of compressor
➔
compressor, outdoor fan is turned on according to the condition of the room temperature.
3. Protection of the indoor fan from droplet formation (Enclosure
sweat and condensed disposal test)
• Control condition :
The system operates standard operation without this condition as follows.
- Setting temperature <25°C
- Indoor fan speed
≤
low speed
- Outdoor temperature < 31°C
• Control method
- Operation frequency of compressor must be below
➃
(refer to the comp. Freq. table)
- The indoor fan operates at medium speed.
Comp. free
Comp. off
0˚C
7˚C
Indoor pipe
temp.
Comp. free
Comp. Step 4
3˚C
3
°
C
Indoor pipe
temp.