background image

2. Pumping down 

• Procedure 

(1) Confirm that both the 2-way and 3-way valves

are set to the open position.  
–  Remove the valve stem caps and confirm that

the valve stems are in the raised position. 

– Be sure to use a hexagonal wrench to operate

the valve stems. 

(2) Operate the unit for 10 to 15 minutes. 

(3) Stop operation and wait for 3 minutes, then

connect the charge set to the service port of
the 3-way valve.
–  Connect the charge hose with the push pin to

the service port.

(4) Air purging of the charge hose.

–  Open the low-pressure valve on the charge set

slightly to air purge from the charge hose. 

(5) Set the 2-way valve to the closed position. 

(6) Operate the air conditioner at the cooling

cycle and stop it when the gauge indicates
1kg/cm

2

g.

(7) Immediately set the 3-way valve to the closed

position.
–  Do this quickly so that the gauge ends up

indicating 3 to 5kg/cm

2

g.

(8) Disconnect the charge set, and mount the 2-

way and 3-way valve’s stem nuts and the
service port nut. 
–  Use torque wrench to tighten the service port

nut to a torque of 1.8 kg.m. 

–  Be sure to check for gas leakage. 

Lo

Closed

Purge the air

Outdoor unit

Indoor unit

Liquid side

Gas side

CLOSE

Open

2-Way
valve

3-Way
valve

CLOSE

-45-

Содержание LS-E0960CD

Страница 1: ...SERVICE MANUAL Room Air Conditioner MODEL LS E0960CL CM CD LS E0960HL HM HD LS F1260CL CM CD LS F1260HL HM HD ...

Страница 2: ...0 Wiring Diagram 11 Operation Details 13 Display Function 21 Self diagnosis Function 21 Installation 22 Operation 38 Disassembly of the parts Indoor Unit 40 2 way 3 way Valve 43 Cycle Troubleshooting Guide 50 Electronic Parts Troubleshooting Guide 51 Electronic Control Device 58 Schematic Diagram 60 Exploded View Replacement Parts List 62 2 ...

Страница 3: ... 6 7 hours The fan is switched to intermittent or irregular operation The fan speed is automatically switched from high to low speed The louver can be set at the desired position or swing up and down automatically Indoor Unit Operation ON OFF by Remote controller Sensing the Room Temperature Room temperature control Starting Current Control Time Delay Safety Control Indoor Fan Speed Control Operat...

Страница 4: ...High 39 C LOW 11 C Down to 18 C Up to 30 C Cooling OFF ON OFF ON Cancel Sleep Mode Timer ON or Timer OFF 1 2 3 4 5 6 7 Off Timer Fan Operates without cooling or heating Operation Mode Selection Fan Speed Selection Room Temperature Display Temperature Setting Setting the Time or timer Timer Selection Timer Setting Timer Cancel Sleep Operation Airflow Direction Control Air Circulation Mode Reset Dow...

Страница 5: ...77 11 2 Indoor 5 7 15 Outdoor 14 5 25 Indoor 804 245 153 900 280 178 Outdoor 684 624 270 Indoor 7 9 Outdoor 25 28 Refrigerant R 22 g 600 860 Airflow Direction Control Up Down Remocon Type L C D Wireless Liquid inch mm 1 4 6 35 Gas 3 8 9 52 1 2 12 7 Sleeping Operation Drain Hose Connecting Cable 1 0mm2 Power Cord 1 0mm2 Air Circulation Noise Level m3 min dB A 1 Service Valve Motor Output Dimensions...

Страница 6: ...ing 3 062 3 360 10 15 25 25 804 x 245 x 153 900 x 280 x 178 684 x 624 x 270 810 x 555 x 262 7 9 25 35 Refrigerant R 22 g 610 860 Airflow Direction Control Up Down Remocon Type L C D Wireless inch mm 1 4 6 35 3 8 9 52 1 2 12 7 Sleeping Operation Drain Hose Connecting Cable 1 0mm2 Power Cord 1 0mm2 Air Circulation Noise Level Input m3 min dB A 1 Indoor Outdoor Indoor Outdoor Indoor Outdoor Indoor Ou...

Страница 7: ... Installation plate D H W Right rear piping Left rear piping ø70mm ø70mm 50mm 20mm 20mm 80mm ø70mm A A A A Center Right rear piping Left rear piping Center ø70mm MODEL DIM Unit W mm 804 900 H mm 245 280 D mm 153 178 9K Btu Series 12K Btu Series 9K 12K 9K 12K 9K 12K ...

Страница 8: ...nit 9K 12K W L2 L3 L1 D H L4 L5 Gas side 3 way valve Liquid side 2 way valve MODEL DIM unit W mm 684 H mm 640 D mm 270 L1 mm 305 L2 mm 62 L3 mm 472 L4 mm 16 L5 mm 193 9K Btu Cooling Heat Pump 12K Btu Cooling Only 8 ...

Страница 9: ...2 H L3 L4 L5 L6 L7 L8 L9 L10 Liquid side 2 way valve Gas side 3 way valve 9 MODEL 12K Btu Heat Pump DIM unit W mm 801 H mm 555 D mm 262 L1 mm 339 L2 mm 37 L3 mm 543 6 L4 mm 11 4 L5 mm 591 L6 mm 105 L7 mm 105 L8 mm 72 5 L9 mm 86 4 L10 mm 77 ...

Страница 10: ...d inch m m 3 8 1 4 15 7 INDOOR UNIT OUTDOOR UNIT HEAT EXCHANGE EVAPORATOR HEAT EXCHANGE CONDENSER COMPRESSOR ACCUMU LATOR GAS SIDE 3 WAY VALVE LIQUID SIDE 2 WAY VALVE CAPILLARY TUBE CHECK VALVE Heating Model only COOLING HEATING REVERSING VALVE Heating Model Only 1 2 1 4 15 7 9K Btu SERIES 12K Btu SERIES ...

Страница 11: ...TO OUTDOOR UNIT STEP MOTOR LE RI STEP MOTOR UP DOWN 1 L 2 N GN YL GN YL BL BR BL BR BL YL OR BK BR GN YL BR THERMISTOR POWER RD BL BL GN YL BR GN YL BL BL BL BL YL RD BL YL RD GN YL RD BL BR BR BR H C F PTC C S R OLP 1 L 2 N 3854AR6093B FAN MOTOR COMP CAPACITOR BR YL OUTDOOR WIRING DIAGRAM TERMINAL BLOCK TO INDOOR UNIT SUPPORT VALVE 1 Indoor Unit 2 Outdoor Unit 1 9K 12K Btu Cooling Only ...

Страница 12: ... MOTOR STEP MOTOR 1 L 2 N 3 4 GN YL GN YL BL BR BL BR RD BK RD BK BL YL OR BK BR GN YL BR THERMISTOR POWER BL BK BK BL YL YL BR RD BL BR RD GN YL GN YL BL BK RD BR GN YL BL BL PTC 3854AR6093D FAN MOTOR RD BL BR C S R COMP REVERSING VALVE OUTDOOR WIRING DIAGRAM TERMINAL BLOCK TO INDOOR UNIT OLP H C F CAPACITOR 1 L 2 N 3 4 1 Indoor Unit 2 9K 12K Btu Cooling Heating 2 1 Outdoor Unit 9K 2 2 Outdoor Un...

Страница 13: ... procedure is as the following 1st Press the ON OFF Button to operate the unit 2nd Press the Airflow Direction Control Button to swing the vertical louver up and down automatically 3nd Repress the Airflow Direction Control Button to set the vertical louver at a fixed position 3 Cooling Mode Operation When selecting the Cooling Mode Operation the unit will operate according to the setting by the re...

Страница 14: ... OFF LOW OFF Operation Cooling Dry Operation COMPRESSOR SETTING TEMP 0 5 C COMP ON ROOM TEMP SETTING TEMP COMP OFF 3 2 minutes 10 minutes 40 seconds 40 seconds 3 2 minutes maximum 10 minutes maximum 3 minutes 5 Cooling Mode with Sleep Mode Auto Control When selecting the Cooling combined with the Sleep Mode Auto Control the operation diagram is as following The setting temperature will be automati...

Страница 15: ...21 C Heating Over 24 C Cooling Intake Air temp INDOOR FAN SPEED COMPRESSOR ON OFF Fuzzy Speed ON OFF Setting Temp 0 5 C Compressor OFF Setting Temp 0 5 C Compressor ON More than 3 minutes Intake air Temperature Setting Temperature Over 26 C 25 C Over 24 C below 26 C Intake air 1 C Over 22 C below 24 C Intake air 0 5 C Over 18 C below 22 C Intake air temperature below 18 C 18 C Over 18 C below 30 C...

Страница 16: ...ode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as fol lowing Intake Air temp INDOOR FAN SPEED OFF Hot Start Selecting fan speed Selecting fan speed LOW LOW A minimum 10sec 1 min minimum 10sec minimum 10sec A B LOW OFF LOW OFF COMPRESSOR ON OFF ON OFF Setting temp 3 C Compressor OFF A point The indoor pipe temperature to be 3...

Страница 17: ...he indoor fan stops until the evaporator piping temperature will be reached at 28 C The operation diagram is as following 28 C PIPE TEMP INDOOR FAN SPEED OFF LOW SELECTING FAN SPEED COMPRESSOR HOT START BY TEMPERATURE ON 60 sec ...

Страница 18: ... TE2 and the indoor Intake air temperature TR2 and checks indoor pipe temperature TE2 the temperature difference T2 TE2 TR2 and the temperature difference Td T1 T2 of T1 T2 If temperature of indoor pipe is below 32 C Deicing function operates at the priority I condition If temperature of indoor pipe is over 32 C Deicing function operates at the priority II condition If the temperature difference T...

Страница 19: ...untains and dark valleys Through analysis in its chaos simulator Goldstar has successfully created such a feeling of freshness and serenity by analyzing the frequency of natural wind Generally natural wind has the following character frequency Magnitude for example dark valley sea moun tain wind So as to make a similar Natural wind function Indoor fan speed is shifted to high from low or reversely...

Страница 20: ...nal from the remote control it will turn off automatically after 7 hours If you want to use this operation Open the front panel upward and move the slide switch to the Auto Restart position If you do not want to use this operation move the Slide Switch to the Remote control position Slide Switch FORCED OPERATION AUTO RESTART REMOTE CONTROL When you are out for a while move the Slide switch to the ...

Страница 21: ...he evaporator pipe from frosting If the temperature of the indoor pipe is below 0 C after 7 minutes from starting the compressor the compressor and outdoor fan is stopped and then after 3 minutes delay of operating of the compressor when the tempera ture of the indoor pipe is over 7 C the compressor and the outdoor fan is reoperated Operation Indicator Sleep Timer Indicator Timer Indicator Deicer ...

Страница 22: ...tained A place where noise prevention is taken into con sideration Do not install the unit near the door way Ensure the spaces indicated by arrows from the wall ceiling fence or other obstacles If an awning is built over the unit to prevent direct sunlight or rain exposure be careful that heat radiation from the condenser is not restricted There should not be any animals or plants which could be a...

Страница 23: ...anchor bolts Always mount the Installation plate horizontally by aligning the marking off line by means of the thread and a level 2 Drill the piping hole with 70mm dia holecore drill Line according to the arrows marked on lower the left and the right side of the Installation Plate The meeting point of the extended line is the cen ter of the hole Drill the Piping hole at either the right or the lef...

Страница 24: ...or unit onto the copper pipes When the flare nuts are removed from the indoor unit Some gas may leak as some gas is charged to prevent the inside of the pipe from rusting Fit the copper pipe end into the Bar of flare tool about 0 1 0mm higher See illustration Flare the pipe ends 4 Tape the flaring portion to protect it from the dust or damages 90 Slanted Rough Pipe cutter A Bar Bar Clamp handle Re...

Страница 25: ...n pipe Don t connect the cable to the indoor unit Wrap the insulation material around the connect ing portion Glue up the connection portion of drain hose and drain pipe Installation plate Pull Pull To remove the holder press the bottom of chassis near the holder upward and pull the tab out of its hole Tubing holder Pull Press 2 1 Drain hose Indoor Outdoor Connecting cable Connecting piping Drain ...

Страница 26: ...eated on the installation plate by moving it in left and right Tubing holder Hook 1 Push 2 Taping Conecting cable Gas side piping Drain hose Liquid side piping Connecting cable Drain hose Press the lower left and right side of the unit against the Installation Plate until the hooks engage with their slots sound click CAUTION Take care to arrange the piping drain hose and cables as the feature 7 pa...

Страница 27: ... pipe 5 Bend the drain hose and bind the drain hose the piping and the connecting cables altogether Installation plate Pull Pull To remove the holder press the bottom of chassis near the holder upward and pull the tab out of its hole Tubing holder Pull Press 2 1 Drain hose Indoor Outdoor Connecting cable Connecting piping Drain pipe Indoor unit tubing Flare nut Spanner Torque wrench Plastic bands ...

Страница 28: ...7 Wrap the tubing the drain hose and the connect ing cable with tape 8 Indoor unit installation Hook the indoor unit onto the upper portion of installation plate Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate Ensure the hooks are properly seated on the installation plate by moving it left and right CAUTION Take care to arrange the piping drain...

Страница 29: ...e screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could give rise to burn out of the wires 4 Specification of power source 5 Confirm that electrical capacity is sufficient 6 See to it that the...

Страница 30: ... N 2 N 2 N 3 4 3 4 2 N BROWN BLUE G Y BLACK RED BROWN BLUE G Y RED BROWN BROWN BLUE BLACK BLACK G Y RED RED G Y BLUE BROWN BLUE GREEN YELLOW BROWN BLUE GREEN YELLOW 1 Cooling only type 2 Cooling Heating type The power cord connected to the indoor unit should be complied with the following specifications Type H05VV F approved by HAR or SA The connecting cable connected to the indoor and outdoor uni...

Страница 31: ... the securing screws To remove the Grille pull lower the left and right side of the grille toward you slightly tilted and lift it straight upward Two tabs on the top inside edge of chassis are clear of their slots 2 Check the drainage Pour a glass of water on the evaporator Ensure if water flows drain hose of indoor unit without any leakage 5 Checking the Drainage and Connecting the cable to Indoo...

Страница 32: ...nd engage two tabs on the top inside edge of the grille with two slots on the cabinet s top front edge Press the Grille toward to the cabinet until it will be back into place 1 L Terminals on the outdoor unit Terminals on the outdoor unit Terminals on the indoor unit Terminals on the indoor unit 1 L 1 L 1 L 2 N 2 N 2 N 3 4 3 4 2 N BROWN BLUE G Y BLACK RED BROWN BLUE G Y RED BROWN BROWN BLUE BLACK ...

Страница 33: ...gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent 2 Tape the Pipings and Connecting cable from down to up 3 Form the pipings gathered by taping along the exterior wall make the Trap to be required to prevent the room from entering the water 4 Fix the pipings onto the wall by saddle or equiv alent In case of the Outdoor unit to be installed below the positi...

Страница 34: ...nd set it free for one minute 7 Set both liquid and gas side valves to open posi tion with the Hexagonal wrench for the unit oper ation 6 Air Purging of the Piping and Indoor Unit 1 Air purging The air remaining which contains moisture in the refrigeration cycle may cause a malfunction on the compressor 1 Remove the caps from the 2 way and 3 way valves 2 Remove the service port cap from the 3 way ...

Страница 35: ...that of measured at first time Liquid side Gas side CLOSE CLOSE Indoor unit Outdoor unit Closed Closed NOTE The additional gas for air purping has been charged in the outdoor unit However if the flare connections have not been done correctly and there gas leaks a gas cylinder and the charge set will be needed CAUTION Do not leak the gas in the air during air purging Use vaccum pump as far as possi...

Страница 36: ... and maximum allowance length is the basis of reliability Oil trap should be installed per 5 7 meters Numerical value in is for Rotary Comp model CAUTION In case more than 5m Max Piping Length Ⓐ m Capacity Btu h 7 12K 15 7 4 20 18K 30 20 15 10 4 or 5 40 24K 30K 30 15 4 or 5 40 Max Elevation Ⓑ m Standard Length m Additional Refrig erant g m ...

Страница 37: ...emperature of the intake and dis charge air 2 Ensure the difference between the intake tem perature and the discharge one is more than 8 C Cooling or reversely Heating 1 Connection of power supply 1 Connect the power supply cord to the inde pendent power supply Circuitbreaker is required 2 Prepare the remote controller Insert two batteries provided Remove the battery cover from the remote con trol...

Страница 38: ...e Soft Dry Operation Mode Auto Operation Mode ON Timer Button Used to set the time of starting operation OFF Timer Button Used to set the time of stopping operation Time Setting Button Used to adjust the time Timer Set Button Used to set the timer when the desired time is obtained Timer CANCEL Button Used to cancel the timer operation Sleep Mode Auto Button Used to set Sleep Mode Auto Operation Ai...

Страница 39: ...ation Mode Auto Operation Mode Heating Operation Mode ON Timer Button Used to set the time of starting operation OFF Timer Button Used to set the time of stopping operation Time Setting Button Used to adjust the time Timer Set Button Used to set the timer when the desired time is obtained Timer CANCEL Button Used to cancel the timer operation Sleep Mode Auto Button Used to set Sleep Mode Auto Oper...

Страница 40: ...e up and down air discharge louver to open position horizontally by finger pressure Remove the securing screws 9K Btu models 2EA 12K Btu models 3EA To remove the Grille pull the lower left and right side of the grille toward you slightly tilted and lift it straight upward 1 To remove the sensor housing connect earth conductor step motor conductor with sensor holder Motor Evaporator P C B 40 ...

Страница 41: ...3 To remove the Discharge Grille Remove the securing screw Pressing the right side of the discharge grille downward slightly unhook the discharge grille Pull the discharge grille out from the chassis carefully 4 To remove the Evaporator Remove 3 screws securing the evaporator at the left 1EA at the right 2EA 41 ...

Страница 42: ... tab is clear of the slot 5 To remove the Cross Flow Fan Loosen the screw securing the cross flow fan to the fan motor do not remove Lift up the right side of the cross flow fan and the fan motor separate the fan motor from the cross flow fan Remove the left end of the cross flow fan from the self aligning bearing 42 ...

Страница 43: ... gauge Open Open Open with charging cylinder Open Open Open with charging cylinder Open Open Open Open Works Shipping Air purging Installation Operation Pumping down Transfering Evacuation Servicing Gas charging Servicing Pressure check Servicing Gas releasing Servicing 1 2 3 4 5 6 Valve cap Open position Closed position Pin Service port Service port cap To outdoor unit Flare nut To piping connect...

Страница 44: ...hexagonal wrench to press the valve core pin discharge for three seconds and then wait for one minute Repeat this three times 5 Use torque wrench to tighten the service port nut to a torque of 1 8kg cm 6 Set the 3 way valve to the back seat 7 Mount the valve stem nuts to the 2 way and 3 way valves 8 Check for gas leakage At this time especially check for gas leakage from the 2 way and 3 way valve ...

Страница 45: ...e hose Open the low pressure valve on the charge set slightly to air purge from the charge hose 5 Set the 2 way valve to the closed position 6 Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 1kg cm2 g 7 Immediately set the 3 way valve to the closed position Do this quickly so that the gauge ends up indicating 3 to 5kg cm2 g 8 Disconnect the charge set and moun...

Страница 46: ...t on the 2 way valve 4 Check for gas leakage Check the flare connections for gas leakage 5 Discharge the refrigerant Close the valve on the gas cylinder and discharge the refrigerant until the gauge indicates 3 to 5 kg cm2 g 6 Disconnect the charge set and the gas cylinder and set the 2 way and 3 way valves to the open position Be sure to use a hexagonal wrench to operate the valve stems 7 Mount t...

Страница 47: ...t and discharge the refrigerant until the gauge indicates 0 kg cm2 G If there is no air in the refrigerant cycle the pressure when the air conditioner is not running is higher than 1 kg cm2 G discharge the refrigerant until the gauge indicates 0 5 to 1 kg cm2 G if this is the case it will not be necessary to apply a evacuatin Discharge the refrigerant gradually if it is discharged too suddenly the...

Страница 48: ...or less 3 Close the valve Lo side on the charge set turn off the vacuum pump and confirm that the gauge needle does not move approxima tely 5 minutes after turning off the vacuum pump 4 Disconnect the charge hose from the vacuum pump Vacuum pump oil If the vacuum pump oil becomes dirty or depleted replenish as needed Lo Open Open Vacuum pump 2 Way valve Outdoor unit Liquid side Indoor unit Gas sid...

Страница 49: ...150g each time while operating the air conditioner in the cooling cycle however one time is not sufficient wait approximately 1 minute and then repeat the procedure pumping down pin 4 Immediately disconnect the charge hose from the 3 way valve s service port Stopping partway will allow the gas to be discharged If the system has been charged with liquid refrigerant while operating the air condition...

Страница 50: ...m air humidity When the room air humidity is relativery higher temperature difference is smaller When the room air humidity is relatively lower temperature difference is larger 2 Check temperature and pressure of refrigeration cycle Notice 1 The suction pressure is usually 4 5 6 0 kg cm2 G Cooling at normal condition 2 The temperature can be measured by attaching the thermometer to the low pressur...

Страница 51: ...ion housing for contacting Connector related to CN POWER Connector related to CN MOTOR Connector contacting of Outdoor Fan Compressor Display PWB Ass y Check Check each load Indoor Outdoor Fan Motor Compressor Stepping Motor and contacting condition of related connector PCB Board Operation Check Items Power Transformer Outdoor unit Input Voltage Output Voltage IC01D 7812 Output Indoor Outdoor unit...

Страница 52: ...sor stopped Indoor Fan is driven by a low speed At this point the wind speed is not controlled by the remote controller When operated in the Sleeping Mode the wind speed is set to the low speed by force Check DISP PWB Ass y Voltage between CN DISP1 DC 5V When the detect switch double key inside the remote controller door is fault it is impossible to operate temperature regulating and wind speed se...

Страница 53: ...Check the related circuit of R02H 12 1K R01H 1 0K R04H 6 2K R03H 1 0K Micom No 3 4 Indoor unit Check the indoor temperature sensor is disconnected or not About 10kΩ at 25 C Turn off Main Power Check the electrical wiring diagram of outdoor side Check the abnormal condition for the component of Compressor Outdoor Fan Motor Check the open or short of conmecting wires between indoor and outdoor Check...

Страница 54: ... circuit of indoor Fan Motor The pin NO 63 of Micom and the part for driving SSR the input and output signal of IC01M PIN NO 2 15 Check the pattern Check the SSR SSR Open Indoor Fan Motor never operate SSR short Indoor Fan Motor always operates in case of ON or OFF 4 When indoor Fan does not operate The voltage of PIN NO 1 blue and 3 yellow of CN MOTOR About AC 180V over About AC 50V over SSR is n...

Страница 55: ...N U D Connector If there are no problems after above checks Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver 5 When Vertical Louver does not operate Check the operating circuit of the Vertical Louver Confirm that there is DC 12V between pin RED of CN U D and GND Confirm that there is a soldering short at following terminals Betwe...

Страница 56: ...temperature is disconnected or not about 10KΩ at 25 C Check the indoor pipe temperature is disconnected or not about 5KΩ at 25 C Turn ON Main Power Check the DC voltage on the PWB ASS Y The details of check are as followings Check point Between Micom NO 62 and GND Between IC01M NO 14 and GND Comp ON DC 5V Below DC 1V Comp OFF DC 0V About DC 12V Check point Between Micom NO 54 and GND Between IC02M...

Страница 57: ...in Power Check the electrical wiring diagram of outdoor side Check the abnormal condition for the component of Compressor Outdoor Fan Motor 4 way Check the open or short of connecting wires between indoor and outdoor ...

Страница 58: ...ST NO MODEL P NO OPTIONAL FUNCTION OR1 OR2 OR3 OR4 OR5 OR6 1 LS E0960CL S 6871AQ2420A 12K OPEN 91K 12K 12K 20K 2 LS F1260CL S 6871AQ2420B 12K OPEN 39K 10K 6 8K 12K 3 LS E0960HL S 6871AQ2420C OPEN 5 1K 91K 27K 15K 56K 4 LS F1260HL S 6871AQ2420D OPEN 5 1K 39K 12K 6 8K 15K ...

Страница 59: ... 59 2 Display Ass y P No 6871AQ3265A ...

Страница 60: ...Schematic Diagram 60 9K 12K Btu Cooling Only Series ...

Страница 61: ... 61 9K 12K Btu Heat Pump Series ...

Страница 62: ...Exploded View Replacement Parts List 1 Indoor Unit 9K Btu Series 62 4 2 1 3 11 12 9 7 6 5 22 23 10 25 26 24 28 27 13 14 16 17 15 18 19 20 21 8 29 30 ...

Страница 63: ...AR1476 4781AR1578 2H00511K 2H01159S 4994AR0403A 6871AQ3265A 6871AQ2420 6323AQ2333 4681AR2727H 5251AR2575A 5990AR3720 5009AR1402 5008AR0402B 3531AR2980 3531AR1398 3530AR1351B 3550AR3724B 5230AR2630A 3H01487A 4H03048 Q TY 9K Heat Pump 9K CoolingOnly PLATE INSTALLATING HOLDER TUBE MOTOR ASSY BLOWER CHASSIS ASSY BLOWER ASSY BEARING ASM EVAPORATOR ASM EVAPORATOR TUBE ASSY REMOTE CONTROLLER ASM BOLT SOC...

Страница 64: ...2 Indoor Unit 12K Btu Series 64 10 1 2 5 6 7 8 9 4 3 13 23 20 21 25 24 22 2 22 1 28 26 30 29 27 12 11 14 15 17 18 16 19 31 32 ...

Страница 65: ...00511K 2H01159S 4994AR1339A 6871AQ3265A 6871AQ2420 6323AQ2333 4681AR2727H 5251AR2575A 5990AR2583B 5990AR2584B 4430AR4216A 5009AR1390C 5008AR1220B 3531AR2980 3531AR1391 3530AR1341B 3550AR3592C 5230AR2672A 3H01487A 4H03048 Q TY 12K Heat Pump 12K Cooling Only PLATE INSTALLATING HOLDER TUBE COVER TUBE MOTOR ASSY BLOWER CHASSIS ASSY BLOWER ASSY BEARING ASM EVAPORATOR ASM TUBE ASSY REMOTE CONTROLLER ASM...

Страница 66: ... 66 2 Outdoor Unit 9K 12K Btu Series 4 3 2 24 6 5 29 1 11 12 28 9 10 7 14 30 32 17 33 26 25 19 18 21 16 15 20 8 23 22 13 31 27 ...

Страница 67: ...PROTECTOR 1 1 R 6750U L017A 1 16 5300 CL101A O L P SPRING 1 1 1 R 17 4995AR1046 CONTROL BOX ASSY 1A 1D 1B R 18 4H01008A CLAMP CAPACITOR 1 1 1 R 19 2H01451 SH CAPACITOR 1P 1P 1T R 20 3550 CL001C TERMINAL COVER 1 1 1 R 21 4H00947A NUT TERMINAL COVER 1 1 1 22 3721AR2734B REAR PANEL ASSY 1 1 1 R 23 3550AR2620 COVER CONTROL 1J 1K 1J R 24 3721AR2658 FRONT PANEL ASSY 1D 1D 1E R 25 4H01050A BAND CORD 1 1 ...

Страница 68: ... 68 21 20 19 14 31 28 30 29 5 4 8 7 9 10 11 12 6 2 1 23 22 26 18 16 3 15 13 17 24 25 27 3 Outdoor Unit 12K Btu Heat Pump ...

Страница 69: ...L ASM 5425AR2160D 1 14 CONDENSER ASM 5403AR2409B 1 R 15 CLAMP CAPACITOR 4H01008A 1 16 TERMINAL BLOCK 3H00390A 1 R 3H00390B 1 17 PILLAR TERMINAL 4H03048A R 4H03048J 1 18 SH CAPACITOR 2H01451 1P R 19 MOUNT MOTOR 1H00838A 1 R 20 MOTOR FAN 1H00853M 1 R 21 FAN 5900AR1119A 1 R 22 PLAIN WASHER 1WPA0800014 1 23 FAN NUT 4H02861A 1 24 FRONT PANEL ASSY 3721AR2400C 1 R 25 DISCHARGE GRILLE 1H00850C 1 R 26 BARR...

Страница 70: ...P No 3828AR7190L July 1998 Printed in Korea ...

Отзывы: