Operation Details
1. Time Delay Safety Control
• 3min.
;The compressor operation is delayed for 3 minutes to balance the pressure of cycle.
(Protection of compressor)
• 5sec.
; The indoor fan is delayed for 5 seconds, when operating initially, to prevent noises occurred by the vertical
louver and wind.
• 30sec. ; The 4-way valve is ceased for 30sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode.
2. Airflow Direction Control
• This function is to swing the vertical louver up and down automatically and to set it at a fixed position.
• The procedure is as the following.
1st ; Press the ON/OFF Button to operate the unit.
2nd ; Press the Airflow Direction Control Button to swing the vertical louver up and down automatically.
3nd ; Repress the Airflow Direction Control Button to set the vertical louver at a fixed position.
3. Cooling Mode Operation
• When selecting the Cooling(
) Mode Operation, the unit will operate according to the setting by the
remote controller and the operation diagram is shown below.
-13-
Setting point:
(Cooling)
CLOSED
OPEN
Cooling
Heating
140
°
8
°
8
7
6
5
4
3
2
1
Setting point:
(Heating)
INTAKE AIR TEMP.
SETTING TEMP. +0.5
°
C
(Compressor ON)
SETTING TEMP. -0.5
°
C
(Compressor OFF)
More than
3 minutes
More than
3 minutes
INDOOR FAN SPEED
COMPRESSOR
Selecting
fan speed
Selecting
fan speed
Selecting
fan speed
Low
ON
OFF
ON
ON
OFF
Low