6-3 OTHER ELECTRIC COMPONENTS
No Cooling
Compressor
doesn´t run.
Cause
Check if current flows to
the following components.
a. Starting Devices
Shorted or Broken
b. OLP
Poor contact or shorted.
c. Compressor coil
Coil Shorted.
d. Circuit Parts
Poor contact or shorted.
Replace each
component.
Running state of
Compressor is poor.
The items
described above
are normal.
Check capacity of
OLP.
Check current
flowing in sub-coil
of Compressor.
Check if current
flows to starting
devices.
Check starting
voltage.
Replace the
defective
component.
Raise the voltage.
Replace the
Compressor.
Compressor
Motor Coil.
Lack of Capacity
Shorted
Poor contacting
and broken.
Low Voltage
Fan Motor doesn´t
run.
Checker current
flow of the door
switch.
Check current
flowing in the fan
motor.
Poor contact
Coil is shorted
Replace the
defective
component.
Much frost is on the
evaporator.
Check current flow
of the following
components:
·
Defrost Control
Check current flow
of the following
components:
·
L-CORD, TE-PLATE
Shorted
Replace PTC.
Replace PTC.