3.2 WALL SLEEVE INSTALLATION

3.2.1 Wall Case Installation Data

General 
Generally, units are installed 3" to 5" above the floor
(flush to finished floor installation is possible) as near to
the center of the room as possible; underneath a
window or a glass panel is typical. Normal installation of
the wall case allows installation flexibility; from flush
with the finished interior wall to a minimum of 1/4" of the
wall case extending beyond the finished exterior of the
building. 
Special consideration must be given to installations
where the wall case does not extend a minimum of 1/4"
beyond the finished exterior wall.

Regardless of the installation, there are several things
to consider when selecting a location for installing the
unit. For instance, drapery location could interfere with
air discharge, and placement of furniture may have an
impact on the performance of the unit. The following
information is intended to minimize installation
problems and assure you of trouble-free installation.

Refer to required wall opening dimensions. Minimum
recommended interior and exterior case projection for
standard wall thicknesses are shown in the drawings in
this manual. The case may be installed flush with the
finished indoor wall.

Mounting an outdoor grille or louver section to the
building face may cause a space between the outdoor
coil and the louver section. Air splitters, aligned with the
ends of the outdoor coil, must be installed between the
outdoor coil inlet and outlet air streams. Gaps between
the outdoor coil and the louver section may allow
condenser air recirculation and affect the operation of
the unit. See the Architecture Grille Aluminum.

For new construction, early planning with the architect
is necessary. Unit location, electrical connection
locations, and wall openings of the proper dimensions
are essential to avoid the necessity of rework, fillers,
framing, moving electrical outlets, and other expensive

modifications. 

For existing construction it is important that carpentry,
masonry and electrical work be performed by
competent, qualified personnel. Since installations in
existing construction may involve removal of
building material from the structure, locating the
wall case must be done correctly.

The wall case should be level from side to side
and from level to 1/4 bubble tilt to the outdoors.
The condensate disposal system in the unit is
designed to dissipate the condensate water
generated during cooling operation in
accordance with ARI standards and actually
uses this water for maximum unit efficiency. A
level unit will also insure proper performance of
the Internal Condensate Removal (ICR) system
optional on heat pump units.

Содержание LP073CD2A

Страница 1: ...onditioner SVC MANUAL Exploded View MODEL LP123CD3A CAUTION Before Servicing the unit read the safety precautions in General SVC manual Only for authorized service personnel Internal Use Only http biz lgservice com ...

Страница 2: ...de Prefilter washable anti fungus Plasma Filter Steps Fan Cool Heat Airflow Direction Control up down Airflow Direction Control left right Remote Controller Type Setting Temperature Cooling Range Heating Auto Operation Micom Control Panel Touch Type Timer Air Discharge Air Ventilation Defrost Control Hot Start Look Cabinet Type Chassis Type Special Function LP123CD3A 3 40 3 46 11 600 11 800 3 08 3...

Страница 3: ...tes to have a time of equalizing the refrigerant pressures for optimizing cycling Fan Only Setting High Low The fan can run at HIGH or LOW speed without COOLING or HEATING to provide air circulation and ventilation Indoor Fan Speed Selections High Low The fan can run at HIGH or LOW speed for either COOLING or HEATING Two Fan motors The unit has two fan motors to provide quiet operation and maximum...

Страница 4: ...y dip switches on control panel from 50 F to 90 F Temperature limits help to prevent overheating and overcooling and reduce energy costs Condensate Drain Valve The unit has a condensate drain valve to prevent water from collecting or freezing in the basepan Quick Heater Recovery The unit is designed to operate the electric heater to warm the room to the temperature set point as soon as heat pump c...

Страница 5: ...sary in the room set the ventilation lever to the OPEN position The damper is opened and outdoor air is drawn into the room This will reduce the cooling or heating efficiency When the air conditioner has performed a cooling or heating operation and is turned off or set to the fan position wait at least 3 minutes before resetting to the cooling operation A slight heat odor may come from the unit wh...

Страница 6: ...uns continually for normal heating operation TIMER SHUT OFF TIME You will usually use shut off time while you sleep If unit is running use Timer to set number of hours until shut off For your sleeping comfort once Time is set the Temperature setting will raise 2 F after 30 minutes and once again after another 30 minutes Push Timer to cycle through the settings from 1 Hour 2 Hours 12 Hours maximum ...

Страница 7: ...fined below for which the LED indicates by flashing number of times the error has been recorded against it The errors are the mentioned which is as follows Electrical Controls ON Normal OFF No power failed board Fault Codes CH 01 Indoor Air Thermistor Error CH 02 Indoor Coil Thermistor Error CH 03 Outdoor Air Thermistor Error PTHP Only CH 04 Outdoor Coil Thermistor Error PTHP Only CH 05 Mode Error...

Страница 8: ...FF 3 OFF 4 OFF 5 LOCAL 1 OFF 2 OFF 3 OFF 4 OFF 5 ON ON REMOTE OFF ON ON ON Remote Local Energy Saver Temperature Limit 1 Temperature Limit 2 Temperature Limit 3 PTAC PTHP UNIT TYPE LOCAL LOCAL 1 OFF OFF 2 OFF OFF 3 OFF OFF 4 OFF OFF 5 LOCAL 1 OFF 2 OFF 3 OFF 4 OFF 5 LOCAL LOCAL 1 OFF OFF 2 OFF OFF 3 OFF OFF 4 OFF OFF 5 LOCAL 1 OFF 2 OFF 3 OFF 4 OFF 5 OFF 6 OFF 7 LOCAL LOCAL 1 OFF OFF 2 OFF OFF 3 O...

Страница 9: ...ch located at the Front Desk Control panel When the front desk switch is ON the fan operates according to the setting without working compressor and heater When the front desk switch is OFF the unit can operate according to the setting of controls REMOTE WALL THERMOSTAT When the wires are connected the unit will be controlled by a remote wall thermostat The thermostat connections supply the 24 Vol...

Страница 10: ...nto place This Room Air Conditioner PTAC discharges air from the top of the unit through reversible 2 position discharge grille louvers The unit is shipped from the factory with the discharge grille louvers at an angle of 40 off vertical In the alternate position the louvers will be at an angle of 15 off vertical To adjust air direction remove the front grille Remove the 4 screws that fasten the d...

Страница 11: ...to section 2 1 1 2 Remove the two screws which fasten the control box See Figure 2 3 Pull the control box from the Air guide 4 Remove the control box cover See Figure 3 5 Disconnect wire housings on the control box 6 Pull the control box assembly out from the unit See Figure 4 7 Re install the components by referring to the removal procedure Figure 2 Figure 3 Figure 4 ...

Страница 12: ...Refer to section 2 1 2 3 Remove the 4 screws which fasten the Evaporator See Figure 5 4 Remove the top cover assembly net steel brace See Figure 6 5 Remove the 6 screws which fasten the Air guide 6 Pull the Air guide assembly out from the unit See Figure 7 7 Remove the 2 screws which fasten the electric heater in the left hand side 8 Pull the electric heater towards left for a while and then lift ...

Страница 13: ...ve the 4 screws which fasten the indoor motor and the earth wire See Figure 10 6 Remove the supports on both sides 7 Pull the cross flow fan out from the air guide 8 Re install the components by referring to the removal procedure 2 2 3 AXIAL FAN 1 Remove the brace 2 Remove the 4 screws which fasten the condenser with the shroud and the basepan See Figure 11 3 Remove the condenser sideways carefull...

Страница 14: ...charge the refrigerant system using a refrigerant recovery system If there is no valve to attach the recovery system install one such as a WATCO A 1 before venting the refrigerant Leave the valve in place after servicing the system 2 Disconnect the 3 leads from the compressor 3 After purging the unit completely unbraze the suction and discharge tubes at the compressor connections 4 Remove the 3 nu...

Страница 15: ...e supply cord of this appliance is damaged it must be replaced by an exact replacement part The special cord means the cord which has the same specification marked on the supply cord fitted to the unit 2 3 6 P C B 1 Remove the escutcheon 2 Remove the two knobs 3 Remove the 2 screws which fasten P C B cover 4 Disconnect all the leads which connected to the P C B 5 Remove the two screws which fasten...

Страница 16: ...Discharge the refrigerant completely 3 Remove the control box assembly Refer to section 2 1 2 4 Remove the 4 screws which fasten the evaporator at the left side and the right side 5 Move the evaporator sideward carefully and then unbraze the interconnecting tube at the evaporator connectors 6 Remove the evaporator 7 Re install the components by referring to notes See Figure 20 2 4 3 CAPILLARY TUBE...

Страница 17: ... at the manifold connection 5 The system is now ready for final charging 6 Recharge as follows 1 Refrigeration cycle systems are charged from the high side If the total charge cannot be put in the high side the balance will be put in the suction line through the access valve which you installed as the system was opened 2 Connect the charging cylinder as shown in Figure 16B With valve C open discha...

Страница 18: ...ent pinch off tool capable of making a vapor proof seal leak detector tubing cutter hand tools to remove components service valve A COMPOUND GAUGE R410A EVAPORATOR LOW PRESSURE SIDE COMPRESSOR CAPILLARY TUBE CONDENSER HIGH PRESSURE SIDE SEE INSETS BELOW MANIFOLD GAUGE B Figure 16 A Pulling Vacuum Figure 16 B Charging A B EXTERNAL VACUUM PUMP COMPOUND GAUGE R410A A CHARGING CYLINDER LOW HI B C ...

Страница 19: ... 3 To improve unit energy efficiency it is recommended the change of outside grille for an unit protection and an addition of a plastic rear grille This is optional 4 Insulation strip prevents the exhaust air from re entering from either side of condenser space which may decrease the cooling efficiency of condenser 406 mm 16 1 066 mm 42 349 mm 13 3 4 505 mm 20 42 13 3 4 16 1 1 2 TYP 1 2 6 21 36 1 ...

Страница 20: ... case may be installed flush with the finished indoor wall Mounting an outdoor grille or louver section to the building face may cause a space between the outdoor coil and the louver section Air splitters aligned with the ends of the outdoor coil must be installed between the outdoor coil inlet and outlet air streams Gaps between the outdoor coil and the louver section may allow condenser air reci...

Страница 21: ...mum exterior dimensions are not met refer to FRAME AND BRICK VENEER INSTALLATION The outside edge of the wall case should extend at least 1 4 beyond the outside wall This is necessary for proper caulking to prevent sealing thedrain holes in the rear flange of the wall case and to facilitate the installation of an accessory drain if used 2 The wall case should be secured to the wall at both sides U...

Страница 22: ... 22 Copyright 2009 LG Electronics Inc All right reserved Only for training and service purposes LGE Internal Use Only ...

Страница 23: ...ASE OUTDOOR GRILLE CAULK CAULK 1 4 MIN POWER SUPPLY CONDUIT WALL RECEPTACLE BY OTHERS FINISHED FLOOR OR TOP OF CARPET Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior CAULK 1 4 CAULK LINTEL ROOM CABINET 2 MIN MOUNTING SCREWS BY INSTALLER WALL CASE OUTDOOR GRILLE SIDE CHANNEL 3 MIN 5 MAX 1 5 16 FINISHED FLOOR OR TOP OF CARPET SUB BASE RAK204 CAULK...

Страница 24: ...or See Figure 1 2 Remove the front gille by pulling it out at the bottom to release it then lift it up along the unit top front See Figure 2 3 Slide the unit into the wall sleeve and secure with 6 screws through the unit flange holes See Figure 3 4 Reinstall the front grille by hooking the top over the unit top then pushing it in at the bottom See Figure 4 Figure 1 Figure 2 Figure 3 Figure 4 ...

Страница 25: ...r supply requirements 3 3 1 ELECTRICAL DATA FOR 208 230V MODEL 3 3 2 ELECTRICAL SAFETY IMPORTANT GROUNDING INSTRUCTIONS The air conditioner has a three prong grounding plug on its power supply cord which must be plugged into properly grounded three prong wall receptacle for your protection against possible shock hazard FUSE Use a time delay fuse or circuit breaker Refer to the nameplate for proper...

Страница 26: ...s Figure 22 3 Install the new door assembly with the key lock by bowing the door with both hands and aligning the door hinge pins with their bracket in the front Figure 23 Important Note Personal Risk Hazard Underwriter s Laboratories Inc listed For institutional use only where supervisory monitoring is available Any other use may increase the risk of personal injury or property damage Note The in...

Страница 27: ...ote it on the delivery receipt Unit must be stored in its original shipping carton in a dry secure place prior to its installation and use Installation The installation and servicing of the equipment referred to in this booklet should be performed by qualified experienced technicians WARNING Hazardous Voltage Disconnect all electric power including remote disconnects before servicing Follow proper...

Страница 28: ...7 Then install one of the three rubber elbows ref Figure 31 at the inlet of the spraying tube and through the rubber grommet 10 Place the top cover assembly back into the unit 11 Install tube 1 and tube 2 ref Figure 31 on the pump assembly using the rubber elbows as shown in Figure 28 12 Position pump assembly to the basepan as shown in Figure 29 and fasten the pump bracket to the basepan using th...

Страница 29: ...own in Figure 32 34 whichever is applicable Make sure to fasten the pump wire through the wire clip on the back side of the control barrier as shown in Figure 33 15 Assembly the unit back following the reverse order of disassembly NOTE All tube should be inserted into rubber elbows by at least 1 2 Figure 31 Pump assembly Tube 1 Tube 2 Rubber elbows 3 Spraying Tube Figure 32 BL BL Figure 34 Figure ...

Страница 30: ...m the sleeve These items may be removed from inside of the building Note The sleeve stiffener must be taken out before the rear sleeve enclosure panel can be removed from the sleeve 2 Prepare the stamped aluminum grille for installation on the sleeve by inserting the six 6 plastic grommets into the square holes located near the outer edges of all four sides of the grille With the grille positioned...

Страница 31: ...er before servicing could result in death or serious injury Important Note The unit OFF switch does not disconnect all electrical power to this unit Receiving Upon receipt of the product inspect the shipping carton for signs of visible damage Report any damage or shortage to the carrier and note it on the delivery receipt The product must be stored in its original shipping carton in a dry secure p...

Страница 32: ... A on the back of blank off plate C and secure the assembly to the left rear of wall sleeve with sheet metal screws provided See Figure 39 for finished left hand side installation If the unit chassis is to be installed right away install the condenser grille to wall sleeve with hardware provided See condenser grille installation instructions If the unit chassis will not be installed right away rep...

Страница 33: ...cted to the drain system inside of the building Install the two blank off plates C and gaskets A on the outdoor portion of the wall sleeve as shown in Figure 40 These components may be installed after the sleeve is secured in the wall opening just prior to the installation of the condenser grille and chassis Leveling Legs Model AYLL101 Description Leveling legs are designed to provide extra front ...

Страница 34: ...side to side Provide a slight slope one quarter bubble in the sight glass toward the outside Check the level again after the unit has been installed Adjust the legs as needed Installation on Wall Sleeve 1 Drill four 1 8 diameter holes in the wall sleeve two on each side using the leveling legs as a template Caulk around screws to prevent water leaks 2 Attach the legs to the wall sleeve using the s...

Страница 35: ...ocedures to ensure the power can not be inadvertently energized Failure to disconnect power before servicing could result in death or serious injury Important Note The unit OFF switch does not disconnect all electrical power to this unit CAUTION Use Copper Conductors Only Unit terminals are not designed to accept other types of conductors Failure to use copper conductors may result in equipment da...

Страница 36: ...iscard the red lead from the wire assembly 2 Connect the black lead to the center terminal of the fuse holder 3 Connect the white lead to the common C terminal on the capacitor 4 Connect the ground wire to the partition panel where the ground wire on the power cord was located Use the supplied green ground screw 5 Connect the white lead of the wire assembly at the junction box to the white lead of...

Страница 37: ... not disconnect all electrical power to this unit CAUTION Use Copper Conductors Only Unit terminals are not designed to accept other types of conductors Failure to use copper conductors may result in equipment damage Important Note All wiring must comply with applicable local and national codes Type and location of fused disconnect switch es must comply with all applicable codes Failure to follow ...

Страница 38: ...older Kit Installation With Subbase See previous section for installation in the control panel 1 Remove both knockouts at the fuse holder location Figure 50 2 Install the fuse holders using screws provided The side connector tab on the fuse holders should be towards the left 3 Connect a stripped BK 9 wire to the center of the quick connect tab of the fuse holders Wire nut the other end of this wir...

Страница 39: ... performed by qualified experienced technicians WARNING Hazardous Voltage Disconnect all electric power including remote disconnects before servicing Follow proper lockout tagout procedures to ensure the power can not be inadvertently energized Failure to disconnect power before servicing could result in death or serious injury Important Note The unit OFF switch does not disconnect all electrical ...

Страница 40: ...onnects before servicing Follow proper lockout tagout procedures to ensure the power can not be inadvertently energized Failure to disconnect power before servicing could result in death or serious injury Important Note The unit OFF switch does not disconnect all electrical power to this unit CAUTION Use Copper Conductors Only Unit terminals are not designed to accept other types of conductors Fai...

Страница 41: ...ring Access Subbase Box Assy Low Voltage Compartment 2 13 16 71 mm 11 13 16 300 mm A B F C E D D E Wall Sleeve Outdoor Side Wall Sleeve Inside Edge Back of Flange A 13 3 4 2 3 4 2 5 8 13 7 8 352 mm 3 1 16 78 mm Left End View Concentric Knockouts In Bottom Ground Screw Location Receptacle Provided Inside subbase Accessory Top View Concentric Knockouts In Rear Field Wiring Line Voltage Field Wiring ...

Страница 42: ...1 to follow the refrigeration cycle and the flow of the refrigerant in the cooling cycle MOTOR COMPRESSOR OIL LIQUID REFRIGERANT CAPILLARY TUBE OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH SUCTION LIME COOL LOW PRESSURE VAPOR COOLED AIR COMPLETE LIQUID BOIL OFF POINT LIQUID PRESSURE DROP ROOM AIR HEAT LOAD VAPOR INLET HOT DISCHARGED AIR LIQUID OUTLET HIGH PRESSURE VAPOR LIQUID PEFRIGERANT LOW ...

Страница 43: ...g Check of outdoor coil heat exchanger the fan operation Check gas leakage Repair gas leak Replacement of unit if the unit is beyond repair Satisfactory operation with temperature difference of inlet outlet air 44 6 50 F 7 10 C Check heat load increase Unexpected residue Overloaded Circuit Check of inside gas pressure Adjusting of refrigerant charge Malfunction of compressor Replacement of compres...

Страница 44: ...capacitor Irregular motor resistance Irregular motor insulation Replacement of fan motor Regular but fails to start Replacement of compressor locking of rotor metal Improper thermostat setting Loose terminal connection Improper wiring Irregular motor resistance Irregular motor insulation Replacement of compressor Motor damaged Drop of power voltage Check capacitor Replacement Only compressor fails...

Страница 45: ... of the fan motor with mounting screw s Check fan motor bearings if motor shaft will not rotate replace the motor Check voltage See limits on this page If not within limits call an electrician Test capacitor Check bearings Does the fan blade rotate freely If not replace fan motor Pay attention to any change from high speed to low speed If the speed does not change replace the motor Check grommets ...

Страница 46: ...eck the position of knob If not at the coldest setting advance the knob to this setting and restart unit Check continuity of the thermostat Replace thermostat if circuit is open Check the capacitor Replace if not within 10 of manufacturers rating Replace if shorted open or damaged Check the compressor for open circuit or ground If open or grounded replace the compressor Check the compressor overlo...

Страница 47: ...e closed over a large area on the coil surface head pressures will increase causing the compressor to cycle Straighten the fins or replace the coil Test capacitor Check the terminals If loose repair or replace Check the system for restriction If restricted clean of replace Close if open Determine if the unit is properly sized for the area to be cooled Check the set screw or clamp If loose or missi...

Страница 48: ... LGE Internal Use Only 6 Piping Diagrams Heat Exchanger Evaporator Heat Exchanger Condenser Capillary Tube Axial Fan Liquid side Th1 Th2 Compressor Gas side C F F LOC Description PCB Connector Th1 Thermistor for indoor Air temperature CN IDAT Th2 Thermistor for Evaporator Pipe temperature CN IDPT ...

Страница 49: ...AN MOTOR Type 2 BK BL RD OR BR YL BK BL RD OR BR YL BK BL RD OR BR YL BK BL RD OR BR YL BK OR BR YL BK BL RD OR BR YL BL OR BR YL RD OR BR YL BL RD OR BR YL BK RD OR BR YL GN YL INDOOR FAN MOTOR Type 3 BK BL RD OR BR YL BK BL OR BR YL BK BL RD OR BR YL BK RD BL BK BK BK BL RD OR BR YL BK OR BR YL OLP BK RD BL F HERM R COMP BL RD OR BR YL GN YL FAN CAPACITOR INDOOR FAN MOTOR OUTDOOR FAN MOTOR INDOO...

Страница 50: ...HEA T E SA VE E SA VE FAN FAN COO L COO L HIG H HIG H LOW LOW TIME R TIME R FAN TIM ER F ON OFF ON OFF ON OFF ON OFF 268711A 268711D 264110 D 346810 152302A 359011 352390 342800 337000 349600A 263230A 263230B 435300A 435300B 261704 135500B 149400 W6631 C 552114 35211A 552113 352116 352115 W52106 8 Exploded View Note Please ensure GCSC since the replacement parts may be changed depending upon the b...

Страница 51: ...P NO MFL63264607 December 2009 ...

Отзывы: