Service Manual 45
Troubleshooting Guide
In general, possible trouble is classified as two causes.
The one is so called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but ineffective cooling
Ineffective Cooling or Heating
Check outdoor coil
(heat exchanger) & fan
operation.
Check gas leakage.
Repair gas leak.
Replacement of unit if the
unit is beyond repair.
Satisfactory operation with
temperature difference of
inlet & outlet air ;
COOLING : 7~10
°
C
HEATING : 15~17
°
C
Check heat load rise at
cooling operation.
Unexpected residue
Added electrical utensil
Check inside gas
pressure.
Adjust refrigerant
charge.
Malfunction of compressor.
Replacement of
compressor
Check of cold (warm) air cir-
culation for smooth flow.
Dirty indoor coil
(heat exchanger.)
Malfunction of fan.
Clogging of air filter.
Obstruction at air outlet.
Stop of auto air-swing.
Countermeasure against
above trouble.
Check clogging in refrigera-
tion circuit.
Repair clogging in refrigera-
tion circuit.
Troubleshooting Guide
Содержание LP-C808FA0
Страница 13: ...Service Manual 13 Wiring Diagram Model LP C808FA0 ...
Страница 14: ...14 Floor Standing Type Air Conditioner Model LP H808FA0 Wiring Diagram ...
Страница 15: ...Service Manual 15 Model LP Z808FA0 Wiring Diagram ...
Страница 58: ...58 Floor Standing Type Air Conditioner Electronic Control Device Electronic Control Device Main P C B ASSY ...
Страница 60: ...60 Floor Standing Type Air Conditioner Electronic Control Device DE ICER P C B ASSY ...
Страница 61: ...Service Manual 61 Circuit and Troubleshooting Schematic Diagram Schematic Diagram ...
Страница 63: ...Service Manual 63 Exploded View and Replacement Parts List 135515 330870 354212 346810 ...
Страница 69: ...P No 3828A30074P April 2005 Printed in Korea ...