Service Manual 23
Installation
2) Indoor Unit installation
➀
The mounting floor should be strong and solid
enough to prevent it from vibration.
➁
Drill the piping hole with 70mm diameter hole-
core drill at either the right or the left of indoor
unit. The hole should be sightly slant to the out-
door side.
3) Outdoor unit Installation
➀
Install the outdoor unit on the concrete or any
solid base securely and horizontally.
➁
If there is any vibration transmitted to the build-
ing, mount the rubber underneath the outdoor
unit.
4) Refrigerant amount
Before shipment, this air conditioner is filled with
the rated amount of refrigerant including additional
amount required for air-purging, subject to 5m pip-
ing length. (The rated amount of refrigerant is indi-
cated on the name plate.) But when the piping
length exceeds 5 meters, additional charge is
required according to the following table.
(Unit: g)
Example) 72K~80K
In case of 10m long pipe(one-way), the amount of
refrigerant to be replenished is:
(10 - 5)
×
80 = 400g
200mm
70mm
70mm
90mm
Wall
Core Drill
MODEL
80K
REFRIGERANT CHARGE
80 per 1m
Содержание LP-C808FA0
Страница 13: ...Service Manual 13 Wiring Diagram Model LP C808FA0 ...
Страница 14: ...14 Floor Standing Type Air Conditioner Model LP H808FA0 Wiring Diagram ...
Страница 15: ...Service Manual 15 Model LP Z808FA0 Wiring Diagram ...
Страница 58: ...58 Floor Standing Type Air Conditioner Electronic Control Device Electronic Control Device Main P C B ASSY ...
Страница 60: ...60 Floor Standing Type Air Conditioner Electronic Control Device DE ICER P C B ASSY ...
Страница 61: ...Service Manual 61 Circuit and Troubleshooting Schematic Diagram Schematic Diagram ...
Страница 63: ...Service Manual 63 Exploded View and Replacement Parts List 135515 330870 354212 346810 ...
Страница 69: ...P No 3828A30074P April 2005 Printed in Korea ...