Service Manual 21
Operation Details
11. Alarm mode display / only displayed while operating.
CH 0
: The sensor for sensing room temperature is open or short.
CH 1
: The sensor for sensing piping temperature of evaporator is open or short.
12. Function for test operation.
This function shall be operated while the set not operating and start while set temperature set button(
▼
) down
and start/stop buttons pressing continuously for 3 seconds.
If you press start/stop button continuously for 3 seconds while set temp down button pressing once more test
operation and the set shall be stopped.
After test operation operating and 18 minutes, test operation and the set shall be stopped.
If you press start/stop button while test operation operating, test operation shall be stopped and the set shall
start.
When test operation operating, the display of
88:88
shall be shifted to tESt
4-way valve is always off when test operation.
Fan speed is high, air purifying system and auto air flow operations are off when test operation.
Regardless of outside temperature, the set operates when test operation.
All but start/stop and air purifying system buttons cannot be set.
13. Function of changing set temperature when re-operation after stop.
Heating operation is set to the previous set temperature when re-operation after stop. Cooling operation is set
to the previous set temperature when re-operation with start/stop button.
1.Operation mode.
Cooling/soft dry mode
→
Cooling mode
Heating mode
→
Heating mode
2. Setting the set temperature when cooling operation.
Room temperature > Set temperature: to be set to the previous set temperature.
Room temperature
≤
Set temperature
a) Room temperature
≥
26°C: to be set to 24°C
b) 22°C
≤
Room temperature
≤
25°C: to be set to 21°C
c) Room temperature
≤
21°C:to be set to -1°C less than room temperature.
3. Setting the set temperature when heating operation.
Set the previous set temperature when stopped.
14. Auto Restart
In case the power comes on again a power failure, Auto Restarting Operation is the function to operate proce-
dures automatically to the previous operating conditions.
Содержание LP-C808FA0
Страница 13: ...Service Manual 13 Wiring Diagram Model LP C808FA0 ...
Страница 14: ...14 Floor Standing Type Air Conditioner Model LP H808FA0 Wiring Diagram ...
Страница 15: ...Service Manual 15 Model LP Z808FA0 Wiring Diagram ...
Страница 58: ...58 Floor Standing Type Air Conditioner Electronic Control Device Electronic Control Device Main P C B ASSY ...
Страница 60: ...60 Floor Standing Type Air Conditioner Electronic Control Device DE ICER P C B ASSY ...
Страница 61: ...Service Manual 61 Circuit and Troubleshooting Schematic Diagram Schematic Diagram ...
Страница 63: ...Service Manual 63 Exploded View and Replacement Parts List 135515 330870 354212 346810 ...
Страница 69: ...P No 3828A30074P April 2005 Printed in Korea ...