20 Room Air Conditioner

Soap water method

1. Remove the caps from the 2-way and 3-way valves.
2. Remove the service-port cap from the 3-way valve.
3. To open the 2-way valve turn the valve stem

counterclockwise approximately 90°, wait for about
2~3 sec, and close it.

4. Apply a soap water or a liquid neutral detergent on

the indoor unit connection or outdoor unit
connections by a soft brush to check for leakage of
the connecting points of the piping.

5. If bubbles come out, the pipes have leakage

1. Connect the charge hose end described in the

preceding steps to the vacuum pump to
evacuate the tubing and indoor unit.
Confirm the "Lo" knob of the manifold valve is
open. Then, run the vacuum pump.
The operation time for evacuation varies with
tubing length and capacity of the pump. The
following table shows the time required for
evacuation.

2. When the desired vacuum is reached, close the

"Lo" knob of the manifold valve and stop the
vacuum pump.

Finishing the job

1. With a service valve wrench, turn the valve stem of

liquid side valve counter-clockwise to fully open the
valve.

2. Turn the valve stem of gas side valve counter-

clockwise to fully open the valve.

3. Loosen the charge hose connected to the gas side

service port slightly to release the pressure, then
remove the hose.

4. Replace the flare nut and its bonnet on the gas side

service port and fasten the flare nut securely with
an adjustable wrench. This process is very
important to prevent leakage from the system.

5. Replace the valve caps at both gas and liquid side

service valves and fasten them tight.

This completes air purging with a vacuum pump.
The air conditioner is now ready for test run.

Test of the leakage

Cap

Hexagonal wrench

A-UNIT

B-UNIT

C-UNIT

Gas side piping

Liquid side piping

Outdoor unit

3-way valve

(Close)

2-way valve

(Open)

2-way valve

(Open)

3-way valve

(Close)

2-way valve

(Open)

3-way valve

(Close)

Required time for evacuation when 30 gal/h vacuum

pump is used

10 min. or more

15 min. or more

If tubing length is less

than 10m (33 ft)

If tubing length is longer

than 10m (33 ft)

Indoor unit

Outdoor unit

Lo

Hi

Manifold valve

Pressure 

gauge

Vacuum pump

Open

Close

Vacuum

Содержание LMNC126LRL0

Страница 1: ...e com techsup html IMPORTANT Please read this installation manual completely before installing the product When the power cord is damaged replacement work shall be performed by authorized personnel only Installation work must be performed in accordance with the national wiring standards by authorized personnel only ...

Страница 2: ...equired Parts Required Tools Installation guide map Four Type A screws plastic anchors Connecting cable Level gauge Screw driver Electric drill Hole core drill ø50mm Horizontal meter Pipes Gas side 1 2 3 8 Liquid side 1 4 Refer to page 7 Insulation materials Additional drain pipe Inner Diameter 20mm Flaring Tools set Specified to torque wrenches 1 8kg m 4 2kg m 5 5kg m 6 6kg m different depending ...

Страница 3: ...rews and plastic anchors Type B screws Holder Remote Control Installation plate Standard Type Side Rear Air intake vents Air outlet vents Piping Drain hose Control cover Connecting wire Side Rear Air intake vents Air outlet vents Piping Drain hose Control cover Connecting wire 48K Btu h 60K Btu h ...

Страница 4: ...to do Be sure to follow the instruction Installation Install the panel and the cover of control box securely There is risk of fire or electric shock Always install a dedicated circuit and breaker Improper wiring or installation may cause fire or electric shock Use the correctly rated breaker or fuse There is risk of fire or electric shock Do not use a defective or underrated circuit breaker Use th...

Страница 5: ...explosion or injury Do not install the product on a defective installation stand It may cause injury accident or damage to the product Be sure the installation area does not deteriorate with age If the base collapses the air conditioner could fall with it causing property damage product failure and personal injury Do not let the air conditioner run for a long time when the humidity is very high an...

Страница 6: ...t To avoid vibration or water leakage Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods It may cause a problem for your neighbors Use two or more people to lift and transport the product Avoid personal injury Do not install the product where it will be exposed to sea wind salt spray directly It may cause corrosion on the product Corrosion pa...

Страница 7: ...cted 2 Ensure that the spaces indicated by arrows around front back and side of the unit 3 Do not place animals and plants in the path of the warm air 4 Take the air conditioner weight into account and select a place where noise and vibration are minimum 5 Select a place so that the warm air and noise from the air conditioner do not disturb neighbors Rooftop Installations If the outdoor unit is in...

Страница 8: ...ty Btu h Total Length m Max Length A B m Max Elevation h1 m In In Elevation h2 m 12k 1 2 1 4 7 5 30 24k 5 8 3 8 7 5 30 Indoor Capacity Btu h Pipe Size Gas Liquid Standard Length Additional Refrigerant m g m h2 h1 A B CAUTION Capacity is based on standard length and maximum allowance length is on the basis of reliability Oil trap should be installed every 5 7 meters ...

Страница 9: ...enterline using a level 2 Measure the wall and mark the centerline It is also important to use caution concerning the location of the installation plate routing of the wiring to power outlets is through the walls typically Drilling the hole through the wall for piping connections must be done safely How to fix installation plate Installation Plate Type A screw Installation plate Ø70mm Left rear pi...

Страница 10: ...he cut cross section of pipe tube 2 Put the end of the copper tube pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing Putting nut on Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal not possible to put them on after flaring work Flaring work Carry out flaring work using flaring tool as show...

Страница 11: ...e Be sure that the drain hose is located at the lowest side of the bundle Locating at the upper side can cause drain pan to overflow inside the unit Inclined Inside is shiny without scratches Smooth all round Even length all round Surface damaged Cracked Uneven thickness Improper flaring Connection of piping Indoor Drain hose Connecting cable Loop Gas side piping Liquid side piping Drain hose CAUT...

Страница 12: ...ighten the flare nut with a wrench 3 When extending the drain hose at the indoor unit install the drain pipe Wrap the insulation material around the connecting portion 1 Overlap the connection pipe insulation material and the indoor unit pipe insulation material Bind them together with vinyl tape so that there is no gap 2 Wrap the area which accommodates the rear piping housing section with vinyl ...

Страница 13: ...h they fit into the rear piping housing section Wrap with vinyl tape Drain hose Pipe Vinyl tape wide CAUTION Installation Information For right piping For right piping follow the instruction below Good case Press on the upper side of clamp and unfold the tubing to downward slowly Bad case Following bending type from left to right could cause problem of pipe damage ...

Страница 14: ...en the flare nut with torque wrench until the wrench clicks When tightening the flare nut with torque wrench ensure the direction for tightening following the arrow on the wrench A UNIT B UNIT C UNIT Gas side piping Liquid side piping Torque wrench Outdoor unit Connection of piping Outdoor Outside diameter Torque mm inch kg m Ø6 35 1 4 1 8 Ø9 52 3 8 4 2 Ø12 7 1 2 5 5 Ø15 88 5 8 6 6 Indoor Capacity...

Страница 15: ... on the Control Cover Inside Outdoor Unit Connect the cable to the Indoor unit CAUTION The circuit diagram is not subject to change without notice Be sure to connect wires according to the wiring diagram Connect the wires firmly so that not to be pulled out easily Connect the wires according to color codes by referring the wiring diagram CAUTION Provide a circuit breaker between power source and t...

Страница 16: ...burn out of the wires 3 Specification of power source 4 Confirm that electrical capacity is sufficient 5 See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate 6 Confirm that the cable thickness is as specified in the power source specification Particularly note the relation between cable length and thickness 7 Do not install an earth l...

Страница 17: ...n the evaporator 2 Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit Drain piping 1 The drain hose should point downward for easy drain flow 2 Do not make drain piping Downward slope Do not raise Accumulated drain water Tip of drain hose dipped in water Air Waving Water leakage Water leakage Ditch Less than 50mm gap Water leakage ...

Страница 18: ...and connecting cable from down to up 2 Secure the tapped piping along the exterior wall using saddle or equivalent In cases where the Outdoor unit is installed above the Indoor unit perform the following 1 Tape the piping and connecting cable from bottom to top 2 Secure the taped piping along the exterior wall Form a trap to prevent water entering the room 3 Fix the piping onto the wall by saddle ...

Страница 19: ...valve with pressure gauge and dry nitrogen gas cylinder to this service port with charge hoses CAUTION Be sure to use a manifold valve for leakage test If it is not available use a stop valve for this purpose The Hi knob of the manifold valve must always be kept close Pressurize the system to no more than 150 P S I G with dry nitrogen gas and close the cylinder valve when the gauge reading reached...

Страница 20: ...service valve wrench turn the valve stem of liquid side valve counter clockwise to fully open the valve 2 Turn the valve stem of gas side valve counter clockwise to fully open the valve 3 Loosen the charge hose connected to the gas side service port slightly to release the pressure then remove the hose 4 Replace the flare nut and its bonnet on the gas side service port and fasten the flare nut sec...

Страница 21: ...the performance Operate unit for 15 20 minutes then check the system refrigerant charge 1 Measure the pressure of the gas side service valve 2 Measure the temperature of the intake and discharge of air 3 Ensure the difference between the intake temperature and the discharge is more than 8 C 4 For reference the gas side pressure of optimum condition is as below Cooling If the actual pressure are hi...

Страница 22: ...port on the gas side service valve 2 Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas 3 Close the liquid side service valve all the way in 4 Turn on the unit s operating switch and start the cooling operation 5 When the low pressure gauge reading becomes 1 to 0 5kg cm2 G 14 2 to 7 1 P S I G fully close the gas side valve stem and then quick...

Отзывы: