Installation Manual 11
ENGLISH
Flaring Work Piping Connection
Check
1. Compare the flared work with figure below.
2. If flare is noted to be defective, cut off the
flared section and do flaring work again.
Preparing the indoor unit's piping and drain hose for installation through the wall.
1. Route the indoor tubing and the drain hose in
the direction of rear left or right
2. Tape the tubing, drain hose and the
connecting cable. Be sure that the drain hose
is located at the lowest side of the bundle.
Locating at the upper side can cause drain
pan to overflow inside the unit.
Inclined
Inside is shiny without scratches
Smooth all round
Even length
all round
Surface
damaged
Cracked Uneven
thickness
= Improper flaring =
Connection of piping - Indoor
Drain hose
Connecting
cable
Loop
Gas side
piping
Liquid side
piping
Drain hose
CAUTION: If the drain hose is
routed inside the room, insulate
the hose with an insulation
material* so that dripping from
"sweating"(condensation) will not
damage furniture or floors.
*Foamed polyethylene or
equivalent is recommended.