Display Function
■
Cooling Model
• Cooling, Soft Dry, Fan
• Sleep Mode
• Timer Mode
Self-diagnosis Function
■
Error Indicator
• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code 12, be sure to pull out power cord and then re-insert.
• Having or not of error code is different from Model.
Operation Indicator
Timer Indicator
Sleep Timer Indicator
Compressor on Indicator
-14-
OUT
DOOR
1
(once)
(once)
(twice)
(twice)
(5times)
(once)
(twice)
(3times)
3sec
3sec
3sec
3sec
3sec
3sec
3sec
3sec
3sec
3sec
3sec
2
3
5
12
Error
Code
Error LED
(Indoor body operation LED)
Error contents
SVC check point
• Indoor suction temperature
thermistor open/short.
• Indoor pipe temperature
thermistor open/short.
• Indoor TH ass'y check
• Outdoor TH ass'y
check
• Resetting of remocon
operating mode
• Communication
line/circuit check
• Primarily check
refrigerant pressure
• Connecting pipe check
• Connecting cable check
• Outdoor suction temperature
thermistor open/short.
• Outdoor pipe temperature
thermistor open/short.
• Abnormal operation of multi
product.
(Simultanueous operation of
cooling and heating)
• Misconnection of connecting
cables
• Poor communication
Содержание LM-2320C2L/M
Страница 1: ...Multi Type Room Air Conditioner SERVICE MANUAL MODEL LM 2320C2L M ...
Страница 44: ... 44 Electronic Control Device 1 Indoor Unit MAIN P C B ASSY 2 Display Ass y ...
Страница 45: ... 45 1 Indoor Unit Schematic Diagram ...
Страница 48: ... 48 B UNIT 9K 10 24 25 23 28 27 21 19 22 7 6 18 4 5 1 2 3 20 9 31 8 15 12 11 16 13 26 14 17 29 30 ...
Страница 52: ...P No 3828A30074X May 2000 Printed in Korea ...