5. Error Mode & Corrective Method
6. Principal part list of controller
7. Principal part list of Main PCB ASM
8. Principal part list of Remote Controller
Error mode
F01
F04
F05
F02
F03
Cause of error
OPEN/SHORT of
room temp.
sensor
OPEN/SHORT of
outdoor pipe
sensor
OPEN/SHORT of
indoor pipe temp.
sensor
OPEN/SHORT of
outdoor room
temp. sensor
Communication
Error
Remark
Sensing condition of error
Voltage of sensing: Over 4.8V
Voltage of sensing: Less than
0.5V
Voltage of sensing: Over 4.8V
Voltage of sensing: Less than
0.5V
1. Check the voltage of "CO1H"
on the remote controller.
2. Check the temp. sensor of
remtote controller.
1. Check the voltage between PIN
1 and 2 of CN-A cycle/CN-B
cycle ON the main PCB.
2. Check the temp. sensor of
remtote controller.
1. Check the voltage between PIN 3
and 4 of CN-A cycle/CN-B cycle.
2. Check the temp. sensor of
indoor pipe.
1. Check the voltage between
PIN 1 and 3 of CN-TEMP
OUT on the main PCB.
2. Check the temp. sensor of
outdoor room.
1. Check the connecting wire
between main PCB remote
controller.
2. Check the input voltage of
remote-controller.
3. Check the wiring of
remote-controller.
Room
temp.(25°C)
= DC 2.5V
Pipe
temp.(25°C)
= DC 2.5V
Pipe temp.(25°C)
= DC 2.2V
Room
temp.(25°C)
= DC 2.2V
Input voltage of
remote-controller
= DC 12V
Voltage of sensing: Over 4.8V
Voltage of sensing: Less than
0.5V
Voltage of sensing: Over 4.8V
Voltage of sensing: Less than
0.5V
Communication interruption
between remote controller and
Main PCB for 2 minutes.
Method of SVC
No
Part No
Part Name
Remarks
1
0ITO874000E
MICOM(Main)
MICOM
2
6920AQ9033F
Relay
3
6212AQ9002J
Oscillator
4
6900AQ9028D
Fuse
5
6102A90001A
Varistor
No
Part No
Part Name
Remark
1
OITO641010B
MICOM(Remote Controller)
MICOM
2
6304A30001C
LCD
3
6871A20043A
Remote C PCB ASM
Cooling Only
4
6871A20043H
Remote C PCB ASM
Heat Pump
LK-0580CH/AH
6871A20085B
6171AQ2138E
LK-0880CH/AH
6323AQ3214M
LK-1080CH/AH 6871A20085D 6711A20007B 6323AQ2333T
(OPTION)
6171AQ2138D Cooling Only
LK-1580CH/AH
6871A20085E
6323AQ2333U
6323AQ3214H
LK-2080CH/AH
6171AQ2138E
LK-0580HH
6871A20085A
6171AQ2138E
LK-0880BHS1
LK-0880HH/BH
6711A20007C 6323AQ2333W
6323AQ3214M
Heat Pump
LK-1080HH/BH 6871A20085C
6323AQ2333X
(OPTION)
6171AQ2138D
LK-1580HH/BH 6871A20085F
6323AQ3214H
Model
Main PCB
ASM
Remote
controller
Pipe
Sensor A
Pipe
Sensor A/B
Return Air
Sensor
Outdoor
Room Sensor
Power
Trans
Remark