reFrigerant PiPing DeSign
3. Non-air conditioned, Typical location: When the piping passes through an indoor area where the indoor unit does not
operate.
•
Hallway or a dormitory or school, etc.
4. Non-air conditioned, Special location: If conditions 1 and 2 below are present.
1. When the piping passes through an indoor area where the indoor unit does not operate.
2. When the humidity is high and there is no air flow in the location where the piping is installed.
•
The thickness of the above insulation material is based on heat conductivity of 0.61 Btu/in/h/ft
2
/°F.
Minimum Refrigerant Pipe Ethylene Propylene Diene Methylene (EPDM) Insulation Wall Thickness Requirements,
continued.
Piping Insulation / condensate drain Piping
Condensate Drain Piping
Condensate drain piping should be constructed out of materials approved by local codes (generally PVC). Slope gradient for the drain should
be 1/50~1/100, and support hangers should be used at 3-5/16 to 5 foot intervals to keep the condensate drainage system stable (see table
below), and to reduce vibration.
Indoor unit
Or
Outdoor unit
Gradient of at least 1 / 50 ~ 1 / 100
Figure 52: Condensate Drain Piping Gradient.
Pipe Diameter (Inches)
13/16 ~ 1-9/16
1-9/16 ~ 2
2-9/16 ~ 4-15/16
Maximum Interval (feet)
≤3.28
≤4
≤5
Table 44: Interval per Drainage Pipe Diameter.
Indoor Unit
Drain Pipe Dia. (inches)
(External / Internal)
Drain Pump
Drain Lift Height (inches)
Amount of Drainage (gpm)
(at 0.4 inches high)
Four-Way Ceiling Cassette
1-1/4 / 1
Standard
31-1/2
0.106
Outdoor Units
See page 47 to 52 for information in reference to outdoor unit placement and condensate drainage.
Indoor Units
The Four-Way Ceiling Cassette indoor units include a factory-installed drain pump. Depending on the location of the indoor unit, condensa-
tion can be drained directly to the outside of the building, or tied into a drainage piping system.
Table 45:
Drain Piping Specifications.
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
duct (HIGH StatIc) | 63
Refrigerant Piping Design and Best Practices