equiPment SeleCtion ProCeDure
Equivalent Piping Length for Piping Components
Table 24:
Cooling Capacity Coefficient Factor.
Component
Size (Inches)
Elbow (ft.)
1/4
3/8
1/2
5/8
3/4
7/8
1
1-1/8
1-1/4
1-3/8
1-1/2
1-5/8
1-3/4
2-1/8
0.5
0.6
0.7
0.8
1.2
1.3
1.5
1.6
1.8
2.0
2.1
2.3
2.5
2.8
Cooling / Heating Correction Factors
For
Four-Way Ceiling Cassette
systems, calculate the equivalent length of the liquid line from the outdoor unit to the indoor unit. Also, deter-
mine the elevation difference of the indoor unit above or below the outdoor unit. Find corresponding cooling or heating capacity correction
factors as shown below. Multiply the correction factors by the cooling or heating capacity obtained from the capacity table using design
conditions. The result is the NET cooling or heating capacity.
Refrigerant Line Length Derates
For air-cooled systems, a capacity correction factor may have to be applied to account for the length of the system’s refrigerant pipe. Rate of
change in capacity due to increased piping lengths is shown below.
Table 25:
Heating Capacity Coefficient Factor.
Piping Length (ft.)
16.4
32.8
49.2
65.6
98.4
131.2
164.0
196.9
229.7
246.0
Rate of Capacity
Change (%)
LC187HV (18,000 Btu/h)
LC247HV (24,000 Btu/h)
100
99.3
97.9
96.6
93.8
91.1
88.4
-
-
-
LC367HV (36,000 Btu/h)
LC427HV (42,000 Btu/h)
100
99.3
97.9
96.6
93.8
91.1
88.4
85.6
82.9
81.5
Table 26: Equivalent Piping Length for Elbows.
Piping Length (ft.)
16.4
32.8
49.2
65.6
98.4
131.2
164.0
196.9
229.7
246.0
Rate of Capacity
Change (%)
LC187HV (18,000 Btu/h)
LC247HV (24,000 Btu/h)
100
99.7
99.2
98.7
97.7
96.6
95.6
-
-
-
LC367HV (36,000 Btu/h)
LC427HV (42,000 Btu/h)
100
99.7
99.2
98.7
97.7
96.6
95.6
94.6
93.5
93.0
Altitude Correction Factor
The impact of air density must be considered on systems installed at a significant altitude above sea level, therefore, locally accepted alti-
tude correction factors must be applied.