Installation Manual
7
Installation
ENGLISH
Ceiling dimension and hanging bolt location
Level gauge
Ceiling
Unit:mm
TQ/TR Chassis
Ceiling board
Unit:mm
TM/TN/TP Chassis
875
(Ceiling opening)
787
(Hanging bolt)
684
(Hanging bolt)
671
875
(Ceiling opening)
840 Unit size
840 Unit siz
e
585~660(Ceiling opening)
517
461
517
585~660(Ceiling opening)
523
570
570
319
The dimensions of the paper model for installation are the same as those of the ceiling opening dimensions.
Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and our is generated.
These may cause heat exchange ef ciency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
Make sure that ventilation fan is enough to cover all noxious gases from this place.
Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.
2. Avoid installng air conditioner in such
places where cooking oil or iron powder is
generated.
3. Avoid places where in ammable gas is
generated.
4. Avoid place where noxious gas is
generated.
5. Avoid places near high frequency
generators.
NOTICE
CAUTION :
This air-conditioner uses a drain pump.
Install the unit horizontally using a
level gauge.
During the installation, care should be
taken not to damage electric wires.
Select and mark the position for xing bolts and piping hole.
Decide the position for xing bolts slightly tilted to the drain
direction after considering the direction of drain hose.
Drill the hole for anchor bolt on the wall.
Use the ventilation fan
for smoke-collecting
hood with suf cient
capacity.
Cooking table
Air conditioner
Take enough
distance
Содержание JRNU09GTPA4
Страница 20: ...P No MFL65920802_v0 MFL65920802 ...