ENGLISH
Installation Manual
11
Installation
Drain piping must have down-slope (1/50 to 1/100): be sure not to
provide up-and-down slope to prevent reversal ow.
During drain piping connection, be careful not to exert extra force
on the drain port on the indoor unit.
The outside diameter of the drain connection on the indoor unit is
32 mm.
Be sure to install heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe VP-25 and
pipe ttings
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Connect the main drain pipe to the exterior
and leave it provisionally until the test
comes to an end.
Feed water to the exible drain hose and
check the piping for leakage.
Be sure to check the drain pump for normal
operating and noise when electrical wiring
is complete.
When the test is complete, connect the
exible drain hose to the drain port on the
indoor unit.
Heat insulation material: Polyethylene foam with thick-
ness more than 8 mm.
Drain test
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
1/50~1/100
MAX 700 mm
Flexible drain hose
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
Flexible drain hose
1/50~1/100 slope
Hanger
distance
Hanger Bracket
Max 700 mm
Flexible drain hose
Insulation
Metal
clamp
Max 300 mm
1~15 m
Drain Piping
CAUTION : The supplied exible drain
hose should not be curved, neither
screwed. The curved or screwed hose
may cause a leakage of water.