Installation Manual
13
ENGLISH
Installation
DIP Switch Setting
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
Function
Description
Setting Off
Setting On
Default
SW1
SW2
SW3
SW4
SW5
SW6
SW7
SW8
Communication
Cycle
Group Control
Dry Contact Mode
Installation
Heater linkage
Ventilator linkage
Vane selection
(Console)
Region selection
Etc.
N/A (Default)
N/A (Default)
Selection of Master or Slave
Selection of Dry Contact
Mode
Fan continuous operation
N/A
Selection of Ventilator link-
age
Selection of up/down side
Vane
Selection tropical region
Spare
-
-
Master
Wired/Wireless remote
controller
Selection of Manual or Auto
operation Mode
Continuous operation Removall
-
Linkage Removal
Up side + Down side Vane
General model
-
-
-
Slave
Auto
-
-
Working
Up side Vane
Only
Tropical model
-
Off
Off
Off
Off
Off
Off
Off
Off
2. Outdoor Unit
1. Indoor Unit
In case that the products meet speci c conditions, Auto addressing function can start automatically
with the improved speed by turning the DIP switch #3 of the outdoor unit and resetting the power.
* Speci c conditions:
- All names of the indoor units are ARNU****4.
- The serial number of Multi V super IV (outdoor units) is after October 2013.
DIP switch 7 segment
Outdoor Unit PCB
Outdoor Unit DIP Switch