37
PIPING AND WIRING FOR INDOOR UNIT
ENGLISH
Electric Heater Wiring
CAUTION
!
Power Cable Specification : The power cord connected to the outdoor unit should be
complied with IEC 60245 or HD 22.4 S4(Rubber insulated cord, type 60245 IEC 66 or
H07RN-F)
20 mm
GN/YL
1 Phase(Ø)
NORMAL
CROSS-SECTIONAL
AREA 6 mm
2
N
L
External power supply
(same dedicated power
supply for the indoor
unit and outdoor unit)
1Ø Electric Heater (For R32)
CAUTION
!
The power cord connected to the outdoor
unit should be complied with IEC 60245 or
HD 22.4 S4 (This equipment shall be
provided with a cord set complying with the
national regulation.)
The connecting cable connected to the
outdoor unit should be complied with
IEC 60245 or HD 22.4 S4 (This equipment
shall be provided with a cord set complying
with the national regulation.)
In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this appliance
must not be supplied through an external switching device, such as a timer, or connected to a
circuit that is regularly switched on and off by the utility.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualified persons in order to avoid a hazard.
When the connection line between the
indoor unit and outdooor unit is over 40 m,
connect the telecommunication line and
power line separately.
GN/
YL
1 Phase(Ø)
20
mm
3 Phase(Ø)
20 mm
GN/
YL
20 mm
GN/
YL
NORMAL
CROSS-SECTIONAL
AREA 0.75 mm
2
Model Name
Area
(mm
2
)
Phase (Ø)
Capacity
(kW)
1
5
4
7
9
12
6
14
16
3
12
2.5
14
16
NORMAL CROSS-SECTIONAL AREA