SERVICE SETTING
ENGLISH
Display
code
Title
Cause of error
Check point & Normal condition
15
Water pipe
overheated
• Abnormal operation of electric
heater
• Leaving water temperature is above
57 °C(R410A)/65 °C(R32)
• If there is no problem in electric heater control, possible
maximum leaving water temperature is 57 °C(R410A)/65
°C(R32)
20
Thermal fuse is
damaged
• Thermal fuse is cut off by abnormal
overheating of internal electric
heater
• Mechanical fault at thermal fuse
• Wire is damaged
• This error will not be happened if temperature of electric
heater tank is below 80 °C