18 Concealed Duct Air Conditioner
Installation of Indoor, Outdoor Unit
Outdoor
Indoor
Control terminal board
Control box
Control box cover
(On which the Electric
Wiring Connection is put)
A
A view
Remote
control cord
Connection
cord between
the indoor unit
and the
outdoor unit
Cord clamper
1
1
Main
power source
Switch box
Circuit Breaker
Main terminal board
Control terminal board
Cord
clamper
Cover control
ELECTRICAL WIRING
Indoor unit
• Remove the control box cover for
electrical connection between the
indoor and outdoor unit.
(Remove crews .)
• Use the cord clamper to fix the cord.
Perform the electrical wiring work according to the
electrical wiring connection.
• All wiring must comply with local
requirements.
• Select a power source that is capable of
supplying the current required by the air
conditioner.
• Use a recognized circuit breaker between
the power source and the unit. A
disconnection device to adequately
disconnect all supply lines must be fitted.
• Capacity of circuit breaker
WIRING CONNECTION
Outdoor unit
• Remove the control cover for wiring
connection.
• Use the cord clamper to fix the cord.
• Earthing work
Connect the cable of diameter 1.6mm2
or more to the earthing terminal
provided in the control box and do
earthing.
Please check !!
Capacity
1 Phase
3 Phase
30k Btu/h
30A
-
36k Btu/h
40A
25A
42k Btu/h
-
25A
48k Btu/h
-
30A
60k Btu/h
-
30A
18k Btu/h
20A
-
24k Btu/h
25A
-