10 Concealed Duct Air Conditioner
Installation of Indoor, Outdoor Unit
Piping length and the elevation
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
CAUTION:
• If 60k Model is installed at a distance of 15m, 900g of refrigerant
should be added (15-7.5) x 110g = 825g
• Capacity is based on standard length and maximun allowance length
is on the basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.
Gas
Liquid
Standard
Max.
Standard
Max.
30k Btu/h
15.88(5/8")
6.35(1/4")
7.5
50
5
30
50
36k Btu/h(1Ø,C/O) 15.88(5/8")
9.52(3/8")
7.5
50
5
30
35
36k Btu/h(3Ø) 15.88(5/8")
6.35(1/4")
7.5
50
5
30
40
48k Btu/h
19.05(3/4")
9.52(3/8")
7.5
50
5
30
70
60k Btu/h
19.05(3/4")
12.7(1/2")
7.5
50
5
30
Capacity
Pipe Size
Length A(m)
Elevation B(m)
*Additional
(Diameter:Ø)
refrigerant(g/m)
18k Btu/h
15.88(5/8")
6.35(1/4")
7.5
50
5
30
25
24k Btu/h
15.88(5/8")
6.35(1/4")
7.5
50
5
30
25
42k Btu/h(C/O) 19.05(3/4")
9.52(3/8")
7.5
50
5
30
60
42k Btu/h(H/P) 19.05(3/4")
9.52(3/8")
7.5
50
5
30
70
110
36k Btu/h(1Ø,H/P) 15.88(5/8")
6.35(1/4")
7.5
50
5
30
50