INSTALLATION INSTRUCTIONS
Ceiling Height Selection
Indoor unit connected to wired remote controller operate as wired remote controller setting.
Cooling performance is enhanced with relation to ceiling height. The highest cooling
performance and efficiency are provide at super high. (Some noise may be generated
according to the level height setting.)
Group Control
This function is only for group control. Please don’t set this function in case of non-group
control.
After setting Group Control of the product, turn off the power then turn it back on after 1
minute.
Installer Setting - Installer Setting Code Table
Installer Setting Code Table
No.
Function
Function Code
Setting Value
Remote Controller LCD
1
Ceiling Height
Selection
1
1 : Standard
2 : Low
3 : High
4 : Super High
2
Group Control
2
0 : Set to Master
1 : Set to Slave
2 : Check Master/Slave
SELF-DIAGNOSIS FUNCTION
LED2
LED1
Red
Green
01
Indoor Air Sensor (Open/Short)
-
1 Time
◑
-
-
02
Indoor In Pipe Sensor (Open/Short)
-
2 Times
◑
-
-
05
Communication Failure (Indoor Unit
↔
Outdoor Unit)
-
5 Times
◑
-
-
06
Indoor Out Pipe Sensor (Open/Short)
-
6 Times
◑
-
-
09
Indoor EEPROM Error
-
9 Times
◑
-
-
10
Indoor Fan Lock Error
1 Time
◑
-
-
-
12
Indoor Middle Pipe Sensor (Open/Short)
1 Time
◑
2 Times
◑
-
-
Error
Code
Indoor Unit
Outdoor Unit
Error Indication
Description