Operation
Heating Mode Operation
Defrost Control(Heating)
• When the intake air temp r3°…above the setting temp, the compressor is turned off. When below
the setting temp, the compressor is turned on.
Compressor ON Temp.
➲
Setting Temp.
Compressor OFF Temp.
➲
Setting Temp.+3°C
• While compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 27°C , it
operates with the low or setting speed. When the indoor pipe temp is between 20°C and 27°C, it operates with
Super-Low(while in sleep mode, with the medium airflow speed).
• While compressor off, the indoor fan is off when the indoor pipe temp is below 33°C, when above 35°C , it
operates with the low airflow speed.
• While in defrost control, the indoor is outdoor fans are turned off.
• Defrost operation is controlled by timer and sensing temperature of outdoor pipe.
• The first defrost starts only when the outdoor pipe temperature falls below -6°C after 35 minutes passed from
starting of heating operation and more than 4 minutes operation of compressor.
• Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature
rises over 15°C even before 12 minutes.
• The second defrost starts only when the outdoor pipe temperature falls below -6°C after 35 minutes passed
from ending of the first defrost and more than 4 minutes operation of compressor.
Auto Changeover
• The air conditioner changes the operation
mode automatically to keep indoor tempera-
ture.
• When room temperature vary over ±2°C with
respect to setting temperature, air condition-
er keeps the room temperature in ±2°C with
respect to setting temperature by auto
change mode.
COOLING
Auto
Change
Mode.
Outdoor temp.
Indoor temp.
Outdoor
temp.
30
°
C
20
°
C
10
°
C
+2
°
C
+1
°
C
+0.5
°
C
Set Temp.
-0.5
°
C
-1
°
C
-2
°
C
HEATING