42
Outdoor Unit
Electrical Wiring
Location of setting Switch
n
Location of setting Switch
Main PCB
SW01B
(DIP S/W)
SW02B
(DIP S/W)
7 - Segment
SW02V
Auto addressing
SW01V
Data confirm
n
Checking according to dip switch setting
1. You can check the setting values of the outdoor unit from the 7 segment LED.
The dip switch setting should be changed when the power is OFF.
2. It checks whether the input is properly performed without the bad contact of the dip switch or not
n
Checking the setting of the unit
The number is sequentially appeared at the 7 segment in 5 seconds after applying the power. This
number represents the setting condition. & model code
‘
total capacity
‘
2
‘
25
‘
model type
1⃞
1 ~255 : model code
2⃞
6~10HP : HP numbers
3⃞
No display : cooling only
2 : heat pump
4⃞
25 : normal
5⃞
ARUV series : 70, ARUN series : 170
Example) ARUN60LL2(R2)
85
‘
6
‘
2
‘
25
‘
170
1⃞ 2⃞ 3⃞ 4⃞
5⃞
CAUTION
Product may not properly operate if the relevant DIP switch is not properly setup.
Model code
Capacity [kW]
Remarks
82
8
Cooling only
83
10
84
5
85
6
Heat pump
86
8