23
ENGLISH
When the power source is supplied to Each outdoor unit individually.
R S T N
Switch
Fuse
L
N
Communication cable
(2 Wires Cable)
Power cable
(4 Wires Cable)
Communication cable
(
3
Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
Power cable
(2 Wires Cable)
[Master]
[Indoor Units]
Outdoor
Power supply
(
3
Ø 4wires)
Indoor
Power supply
(1Ø 2wires)
(Main Switch)
[Slave1]
[Slave2]
[Slave
3
]
R S T N
Switch
Fuse
R S T N
Switch
Fuse
R S T N
Switch
Fuse
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Pull Box
(Installer option)
Frequency
Voltage range(V)
Outdoor
Indoor
60Hz
380V
220V
50Hz
380-415V 220-240V
Slave1
Outdoor Unit
Master
Outdoor unit
Slave2
Outdoor Unit
Slave
3
Outdoor Unit
3
4
3
4
3
4
Master
Outdoor Unit
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
SODU. B SODU. A
IDU. B
IDU. A
CEN. B
CEN. A
DRY1
DRY2
GND
12V
[Heat Pump]
Between Indoor and Master Outdoor unit
The GND terminal at the main PCB is a ‘-’ terminal for dry contact.
It is not the point to make ground connection.
- Make sure that terminal number of master and slave outdoor units
are matched.(A-A,B-B)
WARNING
• Indoor Unit ground wires are required for preventing electrical
shock accident during current leakage, Communication disorder by
noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, mo-
mentary blackout or the power goes on and off while the product is
operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor
and other parts.
!
CAUTION
It should be wiring power cables or communication cables to
avoid interference with the oil level sensor. Otherwise, That oil
level sensor would be operated abnormally.
!
Example) Connection of power and communication cable (UX2)
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm gap
Communication
cable
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm gap
Communication
cable
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm gap
Communication cable
Main power
terminal block
Insulation sleeves
attachments
Fix firmly not
to be displaced
ODU-IDU
Communication cable
ODU-ODU
Communication cable
Main power
terminal block
Ground wire
Power/Ground cable
Over
50mm gap
Communication
cable
Left Side
Right Side
Front Side 1
Front Side 2
Main Power Connection
Communication Connection
Example) Connection of power and communication cable (UX3)
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm gap
Communication
cable
e
wer
Main power
terminal block
Ground wire
Power/
Ground cable
Over
50mm gap
Communication
cable
Left Side
Right Side
Example) Connection of transmission wire
[BUS type]
[STAR type]
- Connection of communication
cable must be installed like
below figure between indoor
unit to outdoor unit.
- Abnormal operation can be
caused by communication de-
fect, when connection of com-
munication cable is installed like
below figure(STAR type).