2) Zoning setting
- Set the address of the valve of the HR unit to the central control address of the connected indoor unit.
- SW01M : selection of the valve to address
SW03M : increase in the digit of 10 of valve address
SW04M : increase in the last digit of valve address
SW05M :Rotary S/W
- Prerequisite for manual valve addressing : central control address of each indoor unit must be preset
differently at its wired remote control.
S/W No.
Setup
No.1
Manual addressing of valve #1
No.2
Manual addressing of valve #2
No.3
Manual addressing of valve #3
No.4
Manual addressing of valve #4
SW03M
Increase in the digit of 10 of valve address
SW04M
Increase in the last digit of valve address
SW05M
Manual addressing of zoning indoor units
SW01M
SW03M
SW04M
SW05M
0
Installation Manual
81
HR Unit PCB
ENGLISH