40 Room Air Conditioner
Operation
6. Heating Operation Mode(only Heating Model)
The unit will operate according to the setting conditions by the remote controller.
The operation diagram is shown below.
INTAKE AIR TEMP.
SETTING TEMP. +6°F
(Compressor OFF)
SETTING TEMP.
(Compressor ON)
Selecting
fan speed
Selecting
fan speed
A
B
A
minimum
10sec.
minimum
1 min.
minimum
10sec.
COMPRESSOR
ON
OFF
ON
OFF
• A point; While the indoor pipe temperature is higher than 95°F, indoor fan operates at low speed. When the
indoor pipe temperature becomes lower than 95°F, indoor fan stops.
• B point; When the indoor pipe temperature is higher than 100°F(38°C), fan operates at selected fan speed.
INDOOR FAN SPEED
Low
OFF
Low
Low
OFF
OFF
OFF
LOW
ON
Selecting
fan speed
INDOOR PIPE
TEMP.
82°F
78°F
1min
INDOOR FAN SPEED
COMPRESSOR
■
Hot-Start Control
• The indoor fan stops until the indoor pipe temperature will be reached at 82°F.
• During heating operation, if indoor pipe temperature falls below 78°F fan stops.
• The operation diagram is shown below.
Содержание ARTCOOL LA091CNP
Страница 47: ...Service Manual 47 Schematic Diagram Schematic Diagram Heat Pump Cooling Only Series Indoor Unit ...
Страница 48: ...48 Room Air Conditioner Schematic Diagram Heat Pump Series Cooling Only Series Outdoor Unit ...
Страница 51: ...Service Manual 51 Schematic Diagram DISPLAY P W B ASM P No 6871A20921A PCB ASSEMBLY ...
Страница 52: ...52 Room Air Conditioner Schematic Diagram Wiring Diagram 1 Indoor Unit Cooling Only Models Heating Models ...
Страница 53: ...Service Manual 53 Schematic Diagram 2 Outdoor Unit Cooling Only Models Heating Models ...
Страница 76: ...P No 3828A20926C December 2006 Printed in Korea ...