58 Room Air Conditioner
Troubleshooting Guide
2) Balance refrigerant of the 3-way valve
(Gas leakage)
• Procedure
(1) Confirm that both the liquid side and gas side
valves are set to the back seat.
(2) Connect the charge set to the 3-way valve’s
port.
– Leave the valve on the charge set closed.
– Connect the charge hose to the service port.
(3) Open the valve (Lo side) on the charge set and
discharge the refrigerant until the gauge indi-
cates 0 kg/cm
2
G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not running
is higher than 1 kg/cm
2
G), discharge the refrig-
erant until the gauge indicates 0.5 to 1
kg/cm
2
G. if this is the case, it will not be neces-
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged.
Lo
Open
Open
3-Way
valve
3-Way
valve
Gas side
CLOSE
OPEN
Outdoor unit
Liquid side
Indoor unit
Содержание ARTCOOL LA091CNP
Страница 47: ...Service Manual 47 Schematic Diagram Schematic Diagram Heat Pump Cooling Only Series Indoor Unit ...
Страница 48: ...48 Room Air Conditioner Schematic Diagram Heat Pump Series Cooling Only Series Outdoor Unit ...
Страница 51: ...Service Manual 51 Schematic Diagram DISPLAY P W B ASM P No 6871A20921A PCB ASSEMBLY ...
Страница 52: ...52 Room Air Conditioner Schematic Diagram Wiring Diagram 1 Indoor Unit Cooling Only Models Heating Models ...
Страница 53: ...Service Manual 53 Schematic Diagram 2 Outdoor Unit Cooling Only Models Heating Models ...
Страница 76: ...P No 3828A20926C December 2006 Printed in Korea ...