Service Manual 47
Troubleshooting Guide
Balance Refrigerant of the 3-way Valve
(Gas leakage)
• Procedure
(1) Confirm that both the 2-way and 3-way
valves are set to the back seat.
(2) Connect the charge set to the 3-way
valve’s port.
– Leave the valve on the charge set closed.
– Connect the charge hose to the service
port.
(3) Open the valve (Lo side) on the charge set
and discharge the refrigerant until the
gauge indicates 0 kg/cm
2
G.
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not
running is higher than 1 kg/cm
2
G), dis-
charge the refrigerant until the gauge indi-
cates 0.5 to 1 kg/cm
2
G. if this is the case, it
will not be necessary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is
discharged too suddenly, the refrigeration
oil will also be discharged.
Lo
Open
Open
3-Way
valve
3-Way
valve
Gas side
CLOSE
OPEN
Outdoor unit
Liquid side
Indoor unit
Содержание Art Cool LS090CE
Страница 62: ...62 Room Air Conditioner Schematic Diagram Schematic Diagram Electric Control Device Indoor ...
Страница 63: ...Service Manual 63 Schematic Diagram Outdoor 9k 12k ...
Страница 64: ...64 Room Air Conditioner Outdoor 18k 24k ...
Страница 65: ...Service Manual 65 Wiring Diagram Indoor Unit Models 9k 12k 18k 24k ...
Страница 66: ...66 Room Air Conditioner Outdoor Unit Models 9k C O Models 12k H P 12k C O H P Schematic Diagram ...
Страница 67: ...Service Manual 67 Models 18k C O Models 18k H P 24k C O H P Schematic Diagram ...
Страница 68: ...68 Room Air Conditioner Schematic Diagram Components Location Indoor MAIN P W B ASSEMBLY TOP VIEW BOTTOM VIEW ...
Страница 69: ...Service Manual 69 Outdoor 9k 12k TOP VIEW BOTTOM VIEW Schematic Diagram ...
Страница 70: ...70 Room Air Conditioner Schematic Diagram Outdoor 18k 24k TOP VIEW BOTTOM VIEW ...
Страница 83: ...P No 3828A20462V Printed in Korea ...