Part 4 Trouble Shooting Guide
7.3.2 Error code 02
Discription
Outdoor TH.(Thermistor) is short or open
• Outdoor TH. is short or open
• Outdoor TH. is not connected to the outdoor unit PCB assembly.
• Damage or defect on the sensing circuit of outdoor unit PCB assembly.
(R03H~R06H, C02H, C03H)
Supposed
Causes
Yes
No
Outdoor TH. is connected to
outdoor unit PCB assembly ?
* Connect to CN-TH1 in outdoor
unit PCB assembly
Outdoor TH. is working
properly?
Yes
No
Sensing circuit of outdoor
unit PCB is operating properly?
Yes
No
* Check outdoor TH.
- Measure resistance of TH.
(air : about 10k
Ω
at 25
°
C,
pipe : about 5k
Ω
at 25
°
C)
- If it is not, replace the thermistor.
* Check soldering state of
R03H ~ R06H, C02H, C03H
* If it is broken, replace outdoor unit
PCB
* The outdoor unit PCB still has some
problem.
* Replace outdoor unit PCB.
Be sure to disconnect the power cable plug from the plug socket before disassembling the
equipment for a repair. Internal components and circuit boards are at main potential when the
equipment is connected to the power cables. This voltage is extremely dangerous and may
cause death or severe injury if come in contact with it.
Be sure to turn off power switch before connect or disconnect connector, or parts damage may
be occurred.