• If the temperature might rise above 30 ℃ or the humidity might rise above RH 80%, attach the Dew-Protective
kit or use another insulation to the indoor body.
h
Dew Protective kit is sold separately.
Use glass wool material or polyethylene foam and make sure at least 10mm thick.
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
• The indoor unit must have the maintenance space.
• The basic installation for the round type should be in an exposed area.
• Do not install at a non exposed installation site such as areas with ceiling texture.
Read completely, then follow step by step.
8
Indoor Unit
Installation
Selection of the best location
h
Please use an annexed sheet or the corrugated
cardboard on the bottom of packing as
installation sheet.
h
When using the bottom sheet, please use it
after separating the installation sheet from
packing of the product floor by using a knife etc
as a picture below.
Annexed sheet
Or
Packing corrugated
cardboard on the
bottom
In case that the unit is installed near the sea, the installation parts may be corroded by salt.
The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
CAUTION
!
Unit:mm
Ceiling
Above 2 500
4 200 or less
1 000
or more
500 or
more
10 or more
500 or
more
300 or less
Floor
F
F
1,2,4 Way
Round
Unit:mm
Floor
Ceiling
Ceiling board
C ≥ 500
C ≥ 500
D ≥ 1 000
B ≥ 10
E ≥ 300
A
F
F
Model
A
4 Way
1.6~10.0 kW
2 000 < A ≤ 3 600
10.0~14.5 kW
2 500 < A ≤ 4 200
2 Way
1 800 < A ≤ 3 300
1 Way
1 800 < A ≤ 3 300
Installation
F
Flat washer for M10
(accessory)
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Nut
(W3/8 or M10)
Ceiling board
Ceiling board
• The following parts are local purchasing.
①
Hanging Bolt - W 3/8 or M10
②
Nut - W 3/8 or M10
③
Spring Washer - M10
④
Plate Washer - M10
Содержание ARNU36GTYB4