Installation
n
Tighten the flare nut with a wrench.
n
When extending the drain hose at the indoor unit,
install the drain pipe.
6. Wrap the insulation material around the connect-
ing portion.
n
Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.
n
Wrap the area which accommodates the rear pip-
ing housing section with vinyl tape.
n
Bundle the piping and drain hose together by
wrapping them with vinyl tape over the range with-
in which they fit into the rear piping housing sec-
tion.
Torque
wrench
Indoor
unit tubing
Spanner (fixed)
Connection
pipe
Flare nut
Vinyl tape(narrow)
Connection
pipe
Connecting cable
Vinyl tape
(wide)
Wrap with vinyl tape
Indoor
unit pipe
Pipe
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit
drain hose
Plastic bands
Insulation material
10
Indoor Unit
If the split type Indoor unit is installed in a wall hav-
ing hole or opening near by or back side of the unit,
then the air from other side of the wall can come
inside the condition space through that hole/ open-
ing. That air can cause unwanted dew/ water
droplet formation when it comes in contact with
body of the indoor unit. So all hole or opening on
the wall must be blocked very well to avoid water
dropping from the body of the unit.
Tightening torque
Shutoff
valve size
Ø6.4
Ø9.5
Ø12.7
Ø15.9
Ø22.2
Ø25.4
13.5-16.5
18-22
14-17
33-39
50-60
62-75
23-27
13.5-16.5
5.4-6.6
Hexagonal
wrench 4mm
Hexagonal
wrench 6mm
Hexagonal
wrench 10mm
8.1-9.9
27-33
36-44
-
11.5-13.9
22-28
-
Tightening torque N-m(Turn clockwise to close)
Shaft(valve body)
Gas line piping attached to unit
Cap(Valve lid) Service port
Flare nut