Installation Manual
9
Installation
Install the air conditioner in the location that satisfies the following conditions.
• The place shall easily bear a load exceeding four times the indoor unit’s weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
Read completely, then follow step by step.
Front view
(Unit: mm)
(Unit: mm)
Top view
Front
Inspection hole(1)
600 x 600
Inspection hole(2)
600 x 600
Control box
1000
Air outlet vents
Air inlet vents
600
600
More than 20
ENGLISH
Installation
Selection of the best location
CAUTION : In case that the unit is installed near the sea, the installation parts
may be corroded by salt, The installation parts (and the unit) should be taken ap-
propriate anti-corrosion measures.
[Inspection Hole Standard]
Number of
inspection hole
Distance between
false ceiling & actual ceiling
Remarks
1
More than 100cm
Sufficient space in the ceiling for servicing.
2
20cm to 100cm
Insufficient space. Difficult for servicing
Hole size should be more
than the size of IDU.
Less than 20cm
Minimum height for motor replacement.