24
Indoor Unit
How to Set E.S.P?
Setting
value
Static Pressure (mmAq(Pa))
5(49)
6(59)
8(78)
10(98)
12(118)
14(137)
15(147)
70
25.1
-
-
-
-
-
-
75
29.5
26.1
-
-
-
-
-
80
34.0
30.8
25.9
-
-
-
-
85
38.4
35.4
30.6
32.2
-
-
-
90
42.9
40.1
35.2
28.1
21.0
-
-
95
47.3
44.8
39.9
33.1
26.3
19.5
-
100
51.8
49.4
44.6
38.0
31.7
25.2
22.6
105
56.2
54.1
49.2
43.0
37.1
31.0
28.5
110
-
58.8
53.9
47.9
42.4
36.7
34.4
115
-
-
58.6
52.9
47.8
42.5
40.3
120
-
-
-
57.8
53.1
48.2
46.1
125
-
-
-
-
54.2
49.4
47.3
ARNU48GM3A4, ARNU54GM3A4
(Unit: CMM)
Note: 1. The above table shows the correlation between the air rates and E.S.P.
2. Make sure to check and adjust E.S.P (external static pressure) value after the installa-
tion of the product. Otherwise, there is a risk of weak cooling/heating and condensed
water discharge/drop.