Hydro Kit
Installation Manual
49
ENGLISH
System Set-Up
Summary
Example of Fuction Code Display
Function Code
Value #1
Value #2
Function
Default
Value #1
Value #2
Remark
Test Run
01:01
01 : Set
-
Disable 3 Min. Delay
02:01
01
-
Remote Air Sensor Connection
03:01
01 : NOT connected.
02 : connected.
-
Celsius/Fahrenheit Switching
04:01
01 : Celsius
02 : Fahrenheit
-
Setting Temp. Selection
05:02
01 : Air Temp.
02 : Leaving water Temp.
-
Auto Dry Contact
06:02
01 : Auto Start OFF
02 : Auto Start ON
-
Address Setting
07:00
00 ~ FF
-
Override Setting
08:00
00 : Slave
01 : Master
-
Water Pump Test Run
09:00
01 : Set
Setting Air Temp.
(cooling Mode)
11:030:018
24°C(75°F)~30°C(86°F)
: Upper Limit of setting range
18°C(64°F)~22°C(71°F)
: Lower Limit of setting range
Setting Leaving Water Temp.
(cooling Mode)
12:024:006
20℃(68℉)~25℃(77℉)
: Upper Limit of setting range
FCU is installed 06℃(42℉)~18℃(64℉)
: Lower Limit of setting range
12:024:016
FCU is not installed 16℃(42℉)~18℃(64℉)
: Lower Limit of setting range
Setting Air Temp.
(Heating Mode)
13:030:016
24℃(75℉) ~ 30℃(86℉)
: Upper Limit of setting range
16℃(60℉) ~ 22℃(71℉)
: Lower Limit of setting range
Setting Leaving Water Temp.
(Heating Mode)
14:050:020
35°C(95°F)~50°C(122°F)
: Upper Limit of setting range
20°C(68°F)~34°C(93°F)
: Lower Limit of setting range
Setting Sanitary Tank Water Temp.
(Sanitary Water Heating)
15:050:040
50°C(122°F)
: Upper Limit of setting range
30°C(86°F)~40°C(104°F)
: Lower Limit of setting range
Operation mode lock
17:00
00 : Off
01 : On
Setting Cut-off Temp.
(FCU Cooling Mode)
22:016:000
16°C(60°F)~25°C(77°F)
00 : FCU is installed
01 : FCU is NOT installed
Setting outdoor Temp. range
(Weather-dependent operation)
23:-10:015
10℃(50℉) ~ 20℃(68℉)
: Upper Limit of setting range
-20℃(-4℉) ~ 05℃(41℉)
: Lower Limit of setting range
Setting indoor air Temp. range
(Weather-dependent operation)
24:021:016
20℃(68℉) ~ 30℃(86℉)
: Upper Limit of setting range
16℃(60℉) ~ 19℃(66℉)
: Lower Limit of setting range
Setting leaving water Temp.
(Weather-dependent operation)
25:050:020
35°C(95°F)~50°C(122°F)
: Upper Limit of setting range
20°C(68°F)~34°C(93°F)
: Lower Limit of setting range
Setting control parameter
(Sanitary water heating operation)
29:003:000
00~01
Setting sanitary water heating timers
2b:030
5 ~ 95 min (step: 5 min)
-
2b:180:020
0 ~ 600 min (step: 30 min)
Setting Water Flow Rate
2c:92
15~92 LPM
-
Changing thermal on/off room air Temp.
2E:00
00~03 : Refer to 52p
-
Changing thermal on/off leaving water Temp.
2F:00
00~03 : Refer to 52p
-
Program version
30:***
Display version number
-
Changing thermal on/off Air temperature
in Cooling Mode
31:00
00~03 : Refer to 52p
Changing thermal on/off temperature in
Cooling Mode
32:00
00~03 : Refer to 52p
Changing thermal on/off sanitary tank
water Temp.
33:00
00~03 : Refer to 52p
Select entering/leaving water Temp mode
in Heating Mode
34:00
00 : Based on leaving water Temp
01 : Based on entering water Temp
Select entering/leaving water Temp mode
in Cooling Mode
35:00
00 : Based on leaving water Temp
01 : Based on entering water Temp
Water Pump operation/delay time set
in Heating Mode
37:000:001
000: Operates according to OFF time setting
001 : Pump always on
001 ~ 060 : OFF Time (minutes)
Water Pump operation/delay time set
in Cooling Mode
38:001:001
000: Operates according to OFF time setting
001 : Pump always on
001 ~ 060 : OFF Time (minutes)
Forced product operation
39:00
00 : Forced product operation in use
01 : Forced product operation not in use
Dry Contact installation set
41:00
00 : Dry Contact equipped decided on
01 : Dry Contact not installed
02 : Dry Contact installed
*Temp. = Temperature
*Sanitary water = Domestic Hot Water
CAUTION:
There is no disinfection function in Hydro Kit.
So, external control equipment should be installed for disinfection function.