Installation
12
Hydro Kit
Foundation for Installation
• Fix the unit tightly with bolts as shown below so that the unit will not fall down due to earthquake.
• Noise and vibration may occur from the floor or wall since vibration is transferred through the in-
stallation part depending on installation status. Thus, use anti-vibration materials (cushion pad)
fully (The base pad shall be more than 200 mm (7-7/8 inch)).
Flat washer
Anchor bolt
Spring washer
Nut
Anti-vibration material
Concrete
base
Support
75(2-15/16)
3 or more screw
threads of the
2 bolts must be
shown
(Unit: mm(inch))
392(15-7/16)
340(13-3/8)
Drain pipe connection
-
Hydro Kit
does not use the drain pump.
- Do not install in upward direction.
- Install the drain pipe in downward direction (1/50-1/100).
-
Hydro Kit
drain connection pipe is PT 1.
Hydro kit
Hydro kit