background image

Installation Manual 

3

ENGLISH

Safety Precautions   

Operation

Do not plug or unplug the
power supply plug during
operation.

• There is risk of fire or electric

shock.

Do not touch(operate) the
product with wet hands.

• There is risk of fire or electrical

shock.

Do not place a heater or other
appliances near the power
cable.

• There is risk of fire and electric

shock.

Do not let the air conditioner run for a long
time when the humidity is very high and a
door or a window is left open.

• Moisture may condense and wet

or damage furniture.

Take care to ensure that power
cable could not be pulled out or
damaged during operation.

• There is risk of fire or electric

shock.

Do not place anything on the
power cable.

• There is risk of fire or electric

shock.

Do not allow water to run into
electric parts.

• It may cause  There is risk of fire,

failure of the product, or electric shock.

Do not store or use flammable
gas or combustibles near the
product.

• There is risk of fire or failure of

product.

Do not use the product in a
tightly closed space for a long
time.

• Oxygen deficiency could occur.

When flammable gas leaks,
turn off the gas and open a
window for ventilation before
turn the product on.

• Do not use the telephone or turn

switches on or off. 
There is risk of explosion or fire

If strange sounds, or small or

smoke comes from product. Turn
the breaker off or disconnect the
power supply cable.

• There is risk of electric shock or

fire.

Stop operation and close the window in
storm or hurricane. If possible, remove
the product from the window before the
hurricane arrives.

• There is risk of property damage,

failure of product, or electric
shock.

Do not open the inlet grill of the
product during operation.
(Do not touch the electrostatic
filter, if the unit is so equipped.)

• There is risk of physical injury,

electric shock, or product failure.

When the product is soaked
(flooded or submerged),
contact an Authorized Service
Center.

• There is risk of fire or electric

shock.

Be cautious that water could
not enter the product.

• There is risk of fire, electric shock,

or product damage.

Ventilate the product from time to time when
operating it together with a stove, etc.

• There is risk of fire or electric shock.

Turn the main power off when cleaning or
maintaining the product.

• There is risk of electric shock.

When the product is not be used for a long
time, disconnect the power supply plug or turn
off the breaker.

• There is risk of product damage or failure, or

unintended operation.

Take care to ensure that nobody could step on
or fall onto the outdoor unit.

• This could result in personal injury and product

damage.

Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress
air or Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion. 

• There is the risk of death, injury, fire or explosion.

For installation, always contact the dealer or
an Authorized Service Center.

• There is risk of fire, electric

shock, explosion, or injury.

Do not install the product on a
defective installation stand.

• It may cause injury, accident, or

damage to the product.

Be sure the installation area
does not deteriorate with age.

• If the base collapses, the air

conditioner could fall with it,
causing property damage, product
failure, and personal injury.

Содержание AQNH09GALA0

Страница 1: ...alling the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly TYPE Floor Standing Console P NO MFL61971201 ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH ...

Страница 2: ...rical work contact the dealer seller a qualified electrician or an Authorized Service Center Do not disassemble or repair the product There is risk of fire or electric shock Always ground the product There is risk of fire or electric shock Install the panel and the cover of control box securely There is risk of fire or electric shock Always install a dedicated circuit and breaker Improper wiring o...

Страница 3: ...w before the hurricane arrives There is risk of property damage failure of product or electric shock Do not open the inlet grill of the product during operation Do not touch the electrostatic filter if the unit is so equipped There is risk of physical injury electric shock or product failure When the product is soaked flooded or submerged contact an Authorized Service Center There is risk of fire ...

Страница 4: ...t cloth to clean Do not use harsh detergents solvents etc There is risk of fire electric shock or damage to the plastic parts of the product Do not touch the metal parts of the product when removing the air filter They are very sharp There is risk of personal injury Do not step on or put anyting on the product outdoor units There is risk of personal injury and failure of product Always insert the ...

Страница 5: ...d the pipe as closely on the wall as possible but be careful that it doesn t break You should purchase the installation parts NOTICE Installation Manual 5 ENGLISH Installation 1 Installation Map 4 8 9 Screw The feature can be changed according to type of model This feature is for single outdoor unit ACCESSORIES 1 Drain Hose 1EA 2 Remote Controller 1EA 3 Remote Controller Holder 1EA 4 Fixing Screw ...

Страница 6: ...r Conditioner 584 125 90 600 160 80 37 100 639 700 666 210 95 45 80 18 82 5 68 5 150 37 140 120 260 5 220 103 51 87 180 647 26 5 140 140 170 170 Installation 2 Drawing of the indoor unit AQNH GALAD Unit mm ...

Страница 7: ...a metal detector to locate studs to prevent unnecessary damage to the wall 7 Keep away from electronic ignition type fluorescent lamps as they may shorten the remote controller range 8 Please check at least 1m away from television or radio It cause interference with the picture or sound 3 Choosing an installation Site More than 300 250 or below from the Floor More than 300 More than 300 Unit mm Be...

Страница 8: ... remove 4 screws dismount the front panel while pulling it forward 4 2 Preparation For Moldings Side Piping and Concealed Installation 4 2 1 For Moldings 1 Remove the slit portions on the Rear Panel 4 2 2 For Concealed Installation 1 Remove the 6 screws 2 Remove the Upper Deco cover 3 Remove the Side Deco covers 4 2 3 For Side Piping Reference 4 2 2 1 Remove the Deco Covers 2 Remove the slit porti...

Страница 9: ...mm in the point indicated by symbol in the illustration as below Unit mm 45 90 75 Left bottom piping Right bottom piping Left right piping Right back piping 60 40 50 Wall 45 90 75 Left back piping Right back piping 45 4 3 Refrigerant Piping The suggested shortest pipe length is 5m in order to avoid noise from the outdoor unit and vibration NOTICE ...

Страница 10: ...e commercial rigid PVC pipe for extension 3 Insulate the indoor drain pipe with 10mm or more of insulation material to prevent condensation 5 7mm 3 16 5 16 Indoor WALL Outdoor 600 Ø17 Unit mm 103 87 4 4 Drill a Hole in the wall 4 5 Drain piping The drain pipe should be inclined downward so that water will flow smoothly without any accumulation NOTICE Do not raise Accumulated drain water Tip of dra...

Страница 11: ...lation 4 6 2 Installation on the Wall 1 Fix up the installation plate using 5 screws and the indoor unit using 4 screws 2 The installation plate should be fixed on a wall which can support the weight of the indoor unit 6 screw M 25L 64 159 700 Unit mm 26 647 180 140 600 574 170 170 210 30 5 30 5 140 160 Installation Plate Molding 4 screw M 25L ...

Страница 12: ... main unit The rear of the unit can be fixed with screws at the points shown in the Fig 2 Be sure to install the supplemental plate in accordance with the depth of the inner wall 670 45 585 200 150 Wall Hole Supplemental plate Field supply 200 150 95 Supplemental plate Field supply 647 170 140 170 140 Unit mm 1 Normal concealed 2 Deep concealed Unit mm Fig 1 ...

Страница 13: ... 4 2 2 2 Insert the Indoor Unit to the Wall hole 3 Secure using 6 screws shown in the illustration Check the horizon of Indoor unit with the wall Please use the Leveler on the drain pan guide Wall Wall 75 50 35 75 Left bottom pipng Left pipng 45 50 Unit mm Right bottom pipng NOTICE Leveler Drain pan Less than 5mm Less than 5mm Less than 5mm ...

Страница 14: ... of the copper tube pipe in a downward direction while removing burrs location is also changed in order to avoid dropping burrs into the tubing Putting nut on Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal not possible to put them on after finishing flare work Flaring work 1 Firmly hold copper pipe in a bar with the dimension shown in...

Страница 15: ...frigerant pipe Refer to next page 4 Assemble the Pipe Bracket 2 screws 5 Put down the Sensor Link 6 After connecting check the pipe arrangement as per illustration 7 The piping can be arranged in six ways as shown in the illustration below 6 Connecting the Piping 3 1 2 6 5 4 Pipe Guide Pipe Guide Connecting Pipe must be placed inner than the pipe guide Connecting Connecting Pipe Pipe Connecting Pi...

Страница 16: ...by wrapping them with vinyl tape sufficient enough to cover where they fit into the rear piping housing section If the drain hose is routed inside the room insulate the hose with an insulation material so that dripping from sweating condensation will not damage furniture or floors Foamed polyethylene or equivalent is recommended mm inch kgf m Ø6 35 1 4 1 8 2 5 Ø9 52 3 8 3 4 4 2 Ø12 7 1 2 5 5 6 5 Ø...

Страница 17: ...ssembly available from the manufacturer of its service agent The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications Rubber insulation type H05RN F approved by HAR or SAA CAUTION 20mm GN YL NORMAL CROSS SECTIONAL AREA 0 75mm2 9k12k 18k Btu h 1 L 2 N 3 Terminal Block of Indoor Unit Outdoor WARNING Make sure that the screws of the terminal a...

Страница 18: ... loose connection can overload and damage electrical components 5 Always ground the air conditioner with a grounding wire and connector to meet the LOCAL REGULATION CAUTION The circuit diagram is not subject to change without notice Be sure to connect wires according to the wiring diagram Connect the wires firmly so that not to be pulled out easily Connect the wires according to color codes by ref...

Страница 19: ...ion re press the button On Off button ON OFF 0 6 sec 1 6 sec 4 sec Ex CH 132 XXO XOX OXX Operation lamp Self Diagnosis Function This unit has an inbuilt error diagnosis capability Error is displayed by RED Operation Lamp Please contact your serviceman dealer in such a situation Prepare remote controller 1 Remove the battery cover by pulling it according to the arrow direction 2 Insert new batterie...

Страница 20: ...s more than 8 C 4 For reference the gas side pressure at optimum condition is shown on table cooling The air conditioner is now ready to use Discharge temperature Discharge air Intake temperature R 410A 35 C 95 F 8 5 9 5kg cm2 G 120 135 P S I G Outside ambient TEMP Refrigerant The pressure of the gas side If the actual pressure is higher than shown the system is most likely over charged and charge...

Страница 21: ...After reading this manual keep it in a place easily accessible to the user for future reference ...

Отзывы: