4. Specifications
6
_ Floor Standing
Floor Standing
Floor Standing
4.1 Indoor Units
Note :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Heating Temperature : Indoor 20°C(68°F) DB / 15°C(59°F) WB
Outdoor 7°C(44.6°F) DB / 6°C(42.8°F) WB
- Interconnected Pipe Length is standard length.
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
Model Name
APNQ36GRA0
APNQ48GTA0
Power Supply
V, Ø, Hz
220-240, 1, 50
220, 1, 60
Power Input (Indoor Unit only)
Rated
W
150
Running Current (Indoor Unit only)
A
0.50
Casing Color
-
Middle White
Dimensions
Body
W x H x D
mm
590 × 1,840 × 320
W x H x D
inch
23-7/32 x 72-7/16 x 12-19/32
Net Weight
Body
kg (lbs)
36.0 (79.4)
Heat
Exchanger
(Row x Column x Fins per inch) x No.
-
(3 x 38 x 19) x 1
Face Area
m
2
(ft
2
)
0.30 (3.26)
Fan
Type
-
Sirocco
Air Flow Rate
SH / H / M / L
m
3
/min
23.5 / 21.0 / 17.0 / 14.0
SH / H / M / L
ft
3
/min
830 / 742 / 600 / 494
Fan Motor
Type
-
BLDC
Output
W x No.
104 x 1
Dehumidification Rate
l
/ h (pts/h)
4.3 (9.1)
Sound Pressure Level
SH / H / M / L
dB(A)
52 / 48 / 44 / 41
Sound Power Level
Cooling
dB(A)
-
Piping
Connections
Liquid
mm(inch)
Ø 9.52 (3/8)
Gas
mm(inch)
Ø 15.88 (5/8)
Drain (O.D. / I.D.)
mm
Ø 21.0 / 17.0
Safety Devices
-
Fuse
-
Thermal Protector for Fan Motor
Power and Communication Cable (included Earth)
No. x mm
2
4C x 1.0
220-240, 1, 50
220, 1, 60
281
0.91
Middle White
590 × 1,840 × 460
23-7/32 x 72-7/16 x 18-1/8
49.0 (108.0)
(3 x 38 x 19) x 1
0.39 (4.17)
Sirocco
38.0 / 32.0 / 28.0 / 24.0
1,342 / 1,130 / 989 / 848
BLDC
224 x 1
5.2 (11.0)
53 / 50 / 47 / 43
-
Ø 9.52 (3/8)
Ø 15.88 (5/8)
Ø 21.0 / 17.0
Fuse
Thermal Protector for Fan Motor
4C x 1.0
Содержание AP-Q100LFA0
Страница 1: ...Floor Standing Cooling Only R410A 50 60Hz 6CSP0 04A Replace 6CSP0 03C P No MFL60778813 ...
Страница 15: ...5 Dimensions 12 _ Floor Standing Floor Standing Floor Standing APNQ60GT3E4 PT3 Chassis ...
Страница 17: ...5 Dimensions 14 _ Floor Standing Floor Standing Floor Standing 5 2 Outdoor Units U4 Chassis APUQ36GRA0 ...
Страница 18: ...5 Dimensions Floor Standing _ 15 Floor Standing Floor Standing U5 Chassis APUQ48GTA0 ...
Страница 19: ...5 Dimensions 16 _ Floor Standing Floor Standing Floor Standing U3 Chassis APUQ60GT3E4 ...
Страница 20: ...5 Dimensions Floor Standing _ 17 Floor Standing Floor Standing APUQ100LFA0 U7 Chassis ...
Страница 25: ...22 _ Floor Standing Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q36GRA0 ...
Страница 26: ...Floor Standing _ 23 Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q48GTA0 ...
Страница 27: ...24 _ Floor Standing Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q60GT3E4 ...
Страница 28: ...Floor Standing _ 25 Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q100LFA0 ...