13. Installation
The unit is completely wired internally at the factory according to general rule of electrical technology, but local
rules, if they are required, should be complied with.
2. Power supply
Power source must fulfill the following conditions:
- The working voltage should be higher than
90% and lower than 110% of the rated voltage
marked on the name plate.
- The starting voltage should be higher than 85%
of the rated voltage marked on the name plate.
Voltage
Time
Starting point
Power source voltage
working voltage
Starting voltage
3. Wiring
After the confirmation of the above conditions, prepare the wiring as follows:
• Use the power supply cord(Rubber insulation, type Ho7RNF approved by HAR or SAA) suitable for the
product's electrical capacity.
• Provide a recognized circuit breaker as below between power source and unit. A disconnection device
to adequately disconnect all supply lines must be fitted. (For service operations)
• The screws which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened.
(If they are loose, it could give rise to burn-out of the wires.)
• See to it that the starting voltage is maintained at more than 90 percent of the rated voltage marked on
the name plate.
• The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the
normal function of a overload protection device.
Capacity Class (kBtu/h)
Ø, V
Main Power Cable
Interconnecting Cable
36k
1Ø, 220-240V
4.0mm
2
x 3C
1.0mm
2
x 4C
48k
5.0mm
2
x 3C
1.0mm
2
x 4C
60k
6.0mm
2
x 3C
1.0mm
2
x 4C
100k
3Ø,380-415V
6.0mm
2
x 5C
1.5mm
2
x 4C
Capacity Class (kBtu/h)
Ø, V
Circuit Breaker
36k
1Ø, 220-240V
30A
48k
40A
60k
40A
100k
3Ø,380-415V
40A
Содержание AP-Q100LFA0
Страница 1: ...Floor Standing Cooling Only R410A 50 60Hz 6CSP0 04A Replace 6CSP0 03C P No MFL60778813 ...
Страница 15: ...5 Dimensions 12 _ Floor Standing Floor Standing Floor Standing APNQ60GT3E4 PT3 Chassis ...
Страница 17: ...5 Dimensions 14 _ Floor Standing Floor Standing Floor Standing 5 2 Outdoor Units U4 Chassis APUQ36GRA0 ...
Страница 18: ...5 Dimensions Floor Standing _ 15 Floor Standing Floor Standing U5 Chassis APUQ48GTA0 ...
Страница 19: ...5 Dimensions 16 _ Floor Standing Floor Standing Floor Standing U3 Chassis APUQ60GT3E4 ...
Страница 20: ...5 Dimensions Floor Standing _ 17 Floor Standing Floor Standing APUQ100LFA0 U7 Chassis ...
Страница 25: ...22 _ Floor Standing Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q36GRA0 ...
Страница 26: ...Floor Standing _ 23 Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q48GTA0 ...
Страница 27: ...24 _ Floor Standing Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q60GT3E4 ...
Страница 28: ...Floor Standing _ 25 Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q100LFA0 ...