_ Floor Standing
Floor Standing
Floor Standing
13. Installation
200mm
70mm
70mm
90mm
Wall
Core Drill
Tilt
Cut if necessary
More than 15mm
Wall
Plastic tube
(Bushing)
INSIDE
OUTSIDE
1. The mounting floor should be strong and solid
enough to prevent it from vibration.
2. Drill the piping hole with 70mm diameter hole-core
drill at either the right or the left of indoor unit. The
hole should be sightly slant to the outdoor side.
3. Insert the plastic tube through the hole.
4. Cut the extruded outside part of the plastic tube, if
necessary.
Outdoor unit Installation
1. Install the outdoor unit on the concrete or any solid base securely and horizontally by securing it with bolts (Ø12mm) and
nuts.
2. If there is any vibration transmitted to the building, mount the rubber underneath the outdoor unit.
Refrigerant amount
Before shipment, this air conditioner is filled with the rated
amount of refrigerant including additional amount required
for air-purging, subject to 7.5m piping length.
(The rated amount of refrigerant is indicated on the name
plate.) But when the piping length exceeds 7.5 meters,
additional charge is required according to the following
table. (100kBtu/h standard piping length = 5 m)
13.2 Installation of Indoor unit and outdoor unit
The Indoor Unit Installation
Capacity Class
Refrigerant charge
36kBtu/h
30g/m
48kBtu/h
40g/m
60kBtu/h
40g/m
100kBtu/h 61g/m
Example)
36kBtu/h: In case of 20m long pipe(one-way), the
amount of refrigerant to be replenished is
(20-7.5)*30=375g
100kBtu/h: In case of 20m long pipe(one-way), the
amount of refrigerant to be replenished is
(20-5)*61= 915g
Содержание AP-Q100LFA0
Страница 1: ...Floor Standing Cooling Only R410A 50 60Hz 6CSP0 04A Replace 6CSP0 03C P No MFL60778813 ...
Страница 15: ...5 Dimensions 12 _ Floor Standing Floor Standing Floor Standing APNQ60GT3E4 PT3 Chassis ...
Страница 17: ...5 Dimensions 14 _ Floor Standing Floor Standing Floor Standing 5 2 Outdoor Units U4 Chassis APUQ36GRA0 ...
Страница 18: ...5 Dimensions Floor Standing _ 15 Floor Standing Floor Standing U5 Chassis APUQ48GTA0 ...
Страница 19: ...5 Dimensions 16 _ Floor Standing Floor Standing Floor Standing U3 Chassis APUQ60GT3E4 ...
Страница 20: ...5 Dimensions Floor Standing _ 17 Floor Standing Floor Standing APUQ100LFA0 U7 Chassis ...
Страница 25: ...22 _ Floor Standing Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q36GRA0 ...
Страница 26: ...Floor Standing _ 23 Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q48GTA0 ...
Страница 27: ...24 _ Floor Standing Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q60GT3E4 ...
Страница 28: ...Floor Standing _ 25 Floor Standing Floor Standing 7 Wiring Diagrams Models AP Q100LFA0 ...