50Hz, R410A _
39
Single Package
Single Package
11. Electrical data
Electrical Characteristics --- Compressor and Outdoor Fan Motor --- 50 Hz
AK-H1208C02
2
AK-H1808C02
3
AK-H2408C02
4
380-415
3
7.0 10.4
74.0 1
5.0 12.2 75.0 2
5.0 12.2 75.0 4
1
0.50
3.40
10.5
380~415
1
0.50 3.40 10.80
1
0.40
2.30
5.20
MODEL
No
Volts Phase
HP
FLA
LRA
No
Volts Phase
HP
FLA
LRA
Compressor
Outdoor Fan Motor
Note
: • FLA-Full Load Amps.
• LRA-Locked Rotor Amps.
Electrical Data Unit wiring
10
AK-H1208C02
380-415
38.2
40.0
40.0
-
-
-
15
AK-H1808C02
380-415
57.2 80.0 80.0 57.8
80.0 80.0
20
AK-H2408C02
380-415
74.4
100.0
100.0
78.5
100.0
100.0
RT
MODEL
Unit Operating
Voltage Range
Standard indoor fan motor
Oversized indoor fan motor
*M.C.A.
*M.F.S.
*M.C.B.
*M.C.A.
*M.F.S.
*M.C.B.
Note:
*M.C.A.: Minimum Circuit Ampacity
*M.F.S. : Maximum Fuse Size
*M.C.B.: Maximum Circuit Breaker
Electrical Data Unit wiring with electric heat pump cycle
9
18
18
36
36
55.3
60.0
60.0
-
-
-
72.4
70.0
70.0
-
-
-
91.4
110.0 110.0 92.0 110.0 110.0
125.5
140.0 140.0 126.1 140.0 140.0
142.8 150.0
150.0 146.9
150.0
150.0
MODEL
Electric
Heater (kW)
Unit Operating
Voltage Range
Standard indoor fan motor
Oversized indoor fan motor
*M.C.A.
*M.F.S.
*M.C.B.
*M.C.A.
*M.F.S.
*M.C.B.
Note:
Heater kW ratings are at 380/415 V unit.
AK-H1208C02
AK-H1808C02
AK-H2408C02
380-415V,
3Ø,
50Hz
Electrical Characteristics --- Evaporator Fan Motor --- 50 Hz
AK-H1208C02
AK-H1808C02
AK-H2408C02
1
3.0 5.0
31.0 1
380-415
3.0
4.0
6.5
26.0
380-415
3
4.0 6.5 26.0 1
380-415
3.0 5.0 7.1 42.0
5.0 7.1 42.0 1
380-415
3.0 7.5 11.2
63.0
MODEL
No
Volts Phase
HP
FLA
LRA
No
Volts Phase
HP
FLA
LRA
Standard evaporator fan motor
Oversized evaporator fan motor
Note
: • FLA-Full Load Amps.
• LRA-Locked Rotor Amps.