10. Performance data
Single Package
30
_ 50Hz, R410A
Single Package
Notes:
1. All capacities are net, indoor fan motor heat is deducted.
2. Capacities are based on the following conditions.
Outdoor air : 85%RH. However, the condition on nominal
capacity is 7°CDB/6°CWB.
3. TC=Total Capacity(SI Unit : kW, English Unit : MBH = kBtu/h.
4. PI=Power Input(Comp.+indoor fan motor+outdoor fan motor) (kW).
5. Air Flow Rate(SI : l/s, English : CFM).
Correction Factor for Heating Capacity due to Frost on Heat Exchanger and Defrosting Operation.
The heating capacity in the "Heating Capacity Table" above indicates the actual heating capacity excluding the effect of frost on the heat
exchanger and the defrosting operation. Therefore, use the following factor to calculate the average heating capacity including capacity
reduction by frost on the exchanger and defrosting operation.
Correction Factor
Outdoor Air Temperature (°FWB, RH=85%)
Correction Factor
14
21.2
24.8
28.4
32
35.6
39.2
42.8
0.95
0.95
0.89
0.87
0.87
0.89
0.91
1.00
15RT AK-H1808C02 (English)
AFR(CFM)
DB(°F)
60.8
64.4
4240
68.0
71.6
75.2
60.8
64.4
5300
68.0
71.6
75.2
60.8
64.4
6360
68.0
71.6
75.2
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
119.7
13.6
141.0
14.8
163.1
16.1
171.3
16.6
179.5
17.1
115.9
14.0
136.5
15.3
157.9
16.7
165.9
17.2
173.8
17.7
112.4
14.5
132.4
15.8
153.2
17.2
160.9
17.8
168.6
18.3
108.4
14.9
127.6
16.3
147.7
17.8
155.1
18.3
162.5
18.9
104.6
15.4
123.3
16.8
142.6
18.3
149.8
18.9
156.9
19.5
121.6
12.4
143.3
13.5
165.7
14.8
174.1
15.2
182.4
15.7
117.8
12.8
138.7
14.0
160.5
15.3
168.5
15.7
176.6
16.2
114.2
13.2
134.6
14.5
155.7
15.8
163.5
16.2
171.4
16.7
110.1
13.7
129.7
14.9
150.1
16.3
157.6
16.8
165.2
17.3
106.3
14.1
125.3
15.4
144.9
16.8
152.2
17.3
159.5
17.8
124.1
11.8
146.1
12.9
169.1
14.1
177.6
14.5
186.1
15.0
120.1
12.2
141.5
13.4
163.7
14.6
172.0
15.0
180.2
15.5
116.6
12.6
137.3
13.8
158.9
15.0
166.8
15.5
174.8
16.0
112.3
13.0
132.3
14.2
153.1
15.5
160.8
16.0
168.5
16.5
108.5
13.4
127.8
14.7
147.9
16.0
155.3
16.5
162.7
17.0
TC
PI
TC
PI
TC
PI
189.6
17.4
205.3
18.3
226.6
19.6
183.6
18.0
198.8
19.0
219.4
20.3
177.1
18.6
192.9
19.6
212.9
21.0
171.7
19.2
185.9
20.2
205.2
21.6
165.8
19.8
179.5
20.8
198.1
22.3
192.7
15.9
208.6
16.8
230.3
18.0
186.6
16.5
202.0
17.3
223.0
18.6
180.0
17.0
196.0
17.9
216.3
19.2
174.5
17.6
188.9
18.5
208.5
19.8
168.5
18.1
182.4
19.1
201.4
20.4
196.6
15.2
212.8
16.0
234.9
17.1
190.4
15.7
206.1
16.6
227.5
17.7
183.6
16.2
200.0
17.1
220.7
18.3
178.1
16.8
192.7
17.6
212.7
18.9
171.9
17.3
186.1
18.2
205.4
19.5
Indoor
Outdoor WB(°F)
14.0
23.0
32.0
35.6
39.2
42.8
50.0
59.0
15RT AK-H1808C02 (SI)
AFR(l/s)
DB(°C)
16.0
18.0
2001
20.0
22.0
24.0
16.0
18.0
2501
20.0
22.0
24.0
16.0
18.0
3001
20.0
22.0
24.0
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
35.0
13.6
41.3
14.8
47.8
16.1
50.2
16.6
52.6
17.1
33.9
14.0
40.0
15.3
46.3
16.7
48.6
17.2
50.9
17.7
32.9
14.5
38.8
15.8
44.9
17.2
47.1
17.8
49.4
18.3
31.7
14.9
37.4
16.3
43.3
17.8
45.4
18.3
47.6
18.9
30.6
15.4
36.1
16.8
41.8
18.3
43.9
18.9
46.0
19.5
35.6
12.4
42.0
13.5
48.5
14.8
51.0
15.2
53.4
15.7
34.5
12.8
40.6
14.0
47.0
15.3
49.4
15.7
51.7
16.2
33.5
13.2
39.4
14.5
45.6
15.8
47.9
16.2
50.2
16.7
32.3
13.7
38.0
14.9
44.0
16.3
46.2
16.8
48.4
17.3
31.1
14.1
36.7
15.4
42.5
16.8
44.6
17.3
46.7
17.8
36.3
11.8
42.8
12.9
49.5
14.1
52.0
14.5
54.5
15.0
35.2
12.2
41.5
13.4
48.0
14.6
50.4
15.0
52.8
15.5
34.1
12.6
40.2
13.8
46.5
15.0
48.9
15.5
51.2
16.0
32.9
13.0
38.8
14.2
44.9
15.5
47.1
16.0
49.4
16.5
31.8
13.4
37.4
14.7
43.3
16.0
45.5
16.5
47.7
17.0
TC
PI
TC
PI
TC
PI
55.5
17.4
60.1
18.3
66.4
19.6
53.8
18.0
58.2
19.0
64.3
20.3
51.9
18.6
56.5
19.6
62.4
21.0
50.3
19.2
54.5
20.2
60.1
21.6
48.6
19.8
52.6
20.8
58.0
22.3
56.4
15.9
61.1
16.8
67.4
18.0
54.7
16.5
59.2
17.3
65.3
18.6
52.7
17.0
57.4
17.9
63.4
19.2
51.1
17.6
55.3
18.5
61.1
19.8
49.4
18.1
53.4
19.1
59.0
20.4
57.6
15.2
62.3
16.0
68.8
17.1
55.8
15.7
60.4
16.6
66.6
17.7
53.8
16.2
58.6
17.1
64.6
18.3
52.2
16.8
56.5
17.6
62.3
18.9
50.4
17.3
54.5
18.2
60.2
19.5
Indoor
Outdoor WB(°F)
-10.0
-5.0
0
2.0
4.0
6.0
10.0
15.0