Installation of Indoor, Outdoor Unit
1) Indoor unit
Install the air conditioner in the location that satisfies the
following conditions.
• The place shall easily bear a load exceeding four
times the indoor unit’s weight.
• The place shall be able to inspect the unit as the fig-
ure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable
dimension “H” is necessary to get a slope to drain as
figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electri-
cal noise.
• The place where air circulation in the room will be
good .
• There should not be any heat source or steam near
the unit
2) Outdoor unit
• If an awning is built over the unit to prevent direct sun-
light or rain exposure, be careful that heat radiation
from the condenser is not restricted.
• There should not be any animals or plants which could
be affected by hot air discharged.
• Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
H
600
600
Top view
(unit: mm)
Front view
Front
Inspection hole
(600X600)
Control box
1000
More than
30cm
More than
30cm
More than
70cm
Sunr
oof
Fence or
obstacles
more than
75cm
more than
25cm
more than
25cm
Installation of Indoor, Outdoor Unit
Selection of the best location