Service Manual
29
Installation of Indoor, Outdoor Unit
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
• Apply a filter Accessory at air return hole.
• Install the unit leaning to a drainage hole side as a
figure for easy water drainage.
• A place where the unit will be leveled and that can
support the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
CASE 1
POSITION OF SUSPENSION BOLT
CASE 2
POSITION OF CONSOLE BOLT
(Unit:mm)
Q
G
R
169
T
E
P
Flat washer
(Zinc plated)
3mm steel chain
1/4" coach
screw
(Self-tapping
wood screw
with hexagonal
head)
Flat washer
Flat washer
(Zinc plated)
(Zinc plated)
Flat washer
(Zinc plated)
Flat washer
(Zinc plated)
2˚
2˚
M6
M6
(Zinc plated)
(Zinc plated)
screw & Nut
screw & Nut
M6
(Zinc plated)
screw & Nut
Galvanized steel
(Pre-punched) strap
1/4" coach
screw
(Self-tapping
wood screw
with hexagonal
head)
Flat washer
(Zinc plated)
Self-tapping
Self-tapping
screw or M6
screw or M6
(Zinc plated)
(Zinc plated)
screw & Nut
screw & Nut
Self-tapping
screw or M6
(Zinc plated)
screw & Nut
TYPE-A (Using steel chain)
TYPE-B (Using Galvanized steel strap)
• Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable
amount of oil steam and flour adhere to the fan, the fin of the
heat exchanger, resulting in heat exchange reduction, spraying,
dispersing of water drops, etc.
In these cases, take the following actions:
• Make sure that the ventilation fan for smoke-collecting hood on
a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air condi-
tioner.
• Make enough distance from a cooking room to install the air
conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where
cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is
stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is
generated.
5. Avoid places near high frequency generators.
E
F
G
P
Q
R
T
Dimension
Model No.
36K
712
284
868
934
937
548
120
42K
712
282
868
934
937
548
120
48K
712
327
935
1014
1014
567
130
60K
712
327
935
1014
1014
567
130
NOTICE
Indoor unit installation