Ceiling concealed duct - Middle static pressure
Indoor unit
Compact
9. Installation
Indoor Units
9.5 Connection pipes to the indoor unit
1) Refrigerant piping work
please refer “REFRIGERANT PIPING WORK”.
2) Piping insulation
①
Perform heat insulation work completely on both gas and
the liquid pipe. Because improper insulation will result
due condensate formation over pipe.
②
Use the heat insulation material for the refrigerant piping
which has an excellent heat resistance (over 120°C).
③
Precautions in high humidity circumstance.
④
Refer to the insulation works.
3) Indoor unit drain piping
①
During drain piping connection, be careful not to exert
extra force on the drain port on the indoor unit.
②
The outside diameter of the drain connection on the
indoor unit is 32mm.
Piping material:
Polyvinyl chloride pipe inner diameter
Ø 25mm and pipe fitting
4) Caution for gradient of unit and drain
piping
- Without drain pump
①
Always lay the drain with downward inclination (1/50 to
1/100).
Prevent any upward flow or reverse flow in any part.
②
10mm or thicker formed thermal insulation shall always
be provided for the drain pipe.
※
U-trap is not required for low static model in which the
external static pressure is below 50 pa(5mm Aq)
Liquid pipe
Refrigerant pipe and thermal
insulation(Local supply)
Union for gas pipe
Insulation
(Local supply)
Clamp for insulation
(Local supply)
Make sure that there is no clearance here.
Overlap with
insulation
Thermal insulation for refrigerant pipe
(Local supply)
Thermal insulation for
piping(Local supply)
• Make sure to insulate any field piping all the way to the
piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.
CAUTION
1. Decline Installation of indoor unit is very important for
the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting
pipe should be 5mm.
CAUTION
Attached drain hose
Bottom of unit
Downward 1/50~1/100 or more
50mm
or more
50mm
or more
Approx 2~3mm