Table 1
8
_
Ceiling concealed duct - Middle static pressure
Indoor unit
Compact
Indoor Units
Setting Value
Static Pressure[mmAq(Pa)]
2.5(25)
4(39)
6(59)
8(78)
100
12.8 -
-
-
105
13.9 -
-
-
110
15.2 12.7
-
-
115
16.5 14.0
-
-
120
17.8 15.3 12.7
-
125
-
16.5 14.0 -
130
-
17.8 15.3 12.6
135
-
-
16.5 13.5
140
-
-
17.5 14.5
145
-
-
-
16.5
Setting Value
Static Pressure[mmAq(Pa)]
2.5(25)
4(39)
6(59)
8(78)
105
13.9 -
-
-
110
15.2 12.7
-
-
115
16.5 14.0
-
-
120
17.8 15.3 12.7
-
125
-
16.5 14.0 -
130
-
17.8 15.3 12.6
135
-
-
16.5 13.5
140
-
-
17.6 14.5
145
-
-
-
16.5
150
-
-
-
18.0
(Unit: CMM)
(Unit: CMM)
Table 2
Model
Mode
Set value
External Static
Pressure
(mmAq(Pa))
CMM
Lower Limit of
External Static
Pressure
(mmAq(Pa))
Upper Limit of
External Static
Pressure
(mmAq(Pa))
ABNW18GBHC0
[UB18C NH0]
High-static
Mode
(Factory Set)
Hl
6(59)
13.5
2.5(25)
8(78)
Mid
12.0
Low
10.5
ABNW24GBHC0
[UB24C NH0]
High-static
Mode
(Factory Set)
Hl
6(59)
18.0
2.5(25)
8(78)
Mid
16.5
Low
14.5
Models : ABNW18GBHC0 [UB18C NH0]
Models : ABNW24GBHC0 [UB24C NH0]
6. External pressure setting for
125
119
114
142
135
125