8.5 Indoor Unit Drain Piping
• Drain piping must have down-slope (1/50 to 1/100): be sure
not to provide up-and-down slope to prevent reversal flow.
• During drain piping connection, be careful not to exert extra
force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the indoor
unit is 32mm.
• Be sure to install heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
• Connect the main drain pipe to the exterior
and leave it provisionally until the test
comes to an end.
• Feed water to the flexible drain hose and
check the piping for leakage.
• Be sure to check the drain pump for normal
operating and noise when electrical wiring
is complete.
• When the test is complete, connect the
flexible drain hose to the drain port on the
indoor unit.
Heat insulation material: Polyethylene foam with
thickness more than 8 mm.
Drain test
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
1/50~1/100
MAX 700mm
Flexible drain hose
Feed water
Drain Pump
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip (accessory)
Flexible drain hose
CAUTION
The supplied flexible drain hose should not be curved,
neither screwed. The curved or screwed hose may
cause a leakage of water.
1/50~1/100
MAX 700mm
Flexible drain hose
Flexible drain hose
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the
circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the
unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they
are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a
overload protection device.
• Proper starting power is not given to the compressor.
CAUTION
Содержание ABNH186HLAC
Страница 19: ...Service Manual 23 Ceiling Cassette 4 way 5 2 Wiring Diagrams Elevation Grill PT HEF PT HFF HDF ...
Страница 71: ...Service Manual 75 MPS Variable SINGLE A II Outdoor Units Introduction 76 MPS Variable SINGLE A 78 ...
Страница 85: ...Service Manual 89 MPS Variable SINGLE A 4 Wiring Diagrams AUUH126C AUUH186C ...
Страница 86: ...Electronic Control Device 90 Universal System Air Conditioner MPS Inverter SINGLE A AUUH246C AUUH306C ...
Страница 87: ...Electronic Control Device Service Manual 91 MPS Inverter SINGLE A AUUH368C AUUH488C ...
Страница 88: ...92 Universal System Air Conditioner MPS Variable SINGLE A AUUH608C ...
Страница 106: ...Electronic Control Device 110 Universal System Air Conditioner Main P C B ASM Ceiling Cassette Type ...
Страница 107: ...Electronic Control Device Service Manual 111 Ceiling Duct Type BH Series ...
Страница 108: ...Electronic Control Device 112 Universal System Air Conditioner BG BR Series ...
Страница 109: ...Electronic Control Device Service Manual 113 VE Series AC DC Ceiling Floor C ...
Страница 110: ...Electronic Control Device 114 Universal System Air Conditioner VB VK VL Series ...
Страница 112: ...Electronic Control Device 116 Universal System Air Conditioner Schematic Diagram Ceiling Cassette Type ...
Страница 113: ...Electronic Control Device Service Manual 117 Schematic Diagram Ceiling Duct Type ...
Страница 114: ...Electronic Control Device 118 Universal System Air Conditioner Schematic Diagram Ceiling Floor ...
Страница 134: ...Outdoor Units 138 Universal System Air Conditioner ...
Страница 135: ...Service Manual 139 VI Exploded View Replacement Parts List Indoor Unit 140 Outdoor Unit 159 Panel Assembly Front 173 ...
Страница 171: ...Exploded View Replacement Parts List Service Manual 175 152312 435310 146811 137211 268712 135802 PT HDA C ...
Страница 175: ...P No 3828A22009P Printed in Korea ...